Specifications

15
LOW TEMPERATURE MINIMUM POSITION (NOT
USED) — The Low Temperature Minimum Position describes
the low temperature limit for Low Outdoor Air Temperature
conditions.
IAQ Pre-Occupancy Purge Algorithm will use this value
whenever Outdoor Air Temperature is below Unoccupied OAT
Lockout Temperature.
Low Temperature
Minimum
Position: Units: Percent
Range: 0 to 100
Default Value: 10.0
HIGH TEMPERATURE MINIMUM POSITION (NOT
USED) The High Temperature Minimum Position specifies
the value for Purge Minimum Damper Position for High
Outdoor Air temperature conditions.
IAQ Pre-Occupancy Purge Algorithm shall use this value
whenever Outdoor Air Temperature is above or at Unoccupied
OAT Lockout Temperature, and also OAT is above Occupied
Cool Set Point or Enthalpy is High. Whenever OAT>=NTLO
and OAT<=OCSP and Enthalpy is Low, the Purge algorithm
will set Purge Minimum Damper Position to 100%.
High Temperature
Minimum
Position: Units: Percent
Range: 0 to 100
Default Value: 35.0
POWER EXHAUST SET POINT (NOT USED) — The Pow-
er Exhaust Set Point describes the minimum damper position
that the Economizer Damper must be before the power exhaust
fan will be energized.
Power Exhaust
Set Point: Units: Percent
Range: 0 to 100
Default Value: 50.0
Table 11 Set Point Configuration
Service Configuration Selection Screen
The
Service Configuration Selection screen is used to configure
the service set points of the PremierLink™ controller. See
Table 12.
COOLING PID The PremierLink controller reads the
space temperature sensor and compares the temperature to
the current high set point. If it exceeds the set point, and
cooling is configured and available, the controller then calcu-
lates the required supply air temperature to satisfy the given
conditions.
The Cooling PID includes the following set points: Propor-
tional Gain, Integral Gain, Derivative Gain, and Starting Value.
Proportional Gain: Range: 0.0 to 40.0
Default Value: 6.0
Integral Gain: Range: 0.0 to 10.0
Default Value: 3.0
Derivative Gain: Range: 0.0 to 20.0
Default Value: 5.0
Starting Value: Units: Degrees F
Range: 40.0 to 90.0
Default Value: 70.0
Table 12 Service Configuration Selection
DESCRIPTION VALUE UNITS NAME
Setpoints
Occupied Low Setpoint 70.0 dF OHSP
Occupied High Setpoint 74.0 dF OCSP
Unoccupied Low Setpoint 69.0 dF UHSP
Unoccupied High Setpoint 75.0 dF UCSP
Hi OAT Lckout for TSTAT
(Not Used)
65.0
dF OATL
Unocc. OAT Lockout TEMP
(Not Used)
50.0
dF NTLO
Unocc. Heating Deadband 1.0 ^F UHDB
Unocc. Cooling Deadband 1.0 ^F UCDB
Low Temp. Min. Position
(Not Used)
10
%LTMP
Hi Temp. Min. Position
(Not Used)
35
%HTMP
Power Exhaust Setpoint
(Not Used)
50
% PES
DESCRIPTION VALUE UNITS NAME
Cooling PID
Proportional Gain 6.0 KP
Integral Gain 3.0 KI
Derivative Gain 5.0 KD
Starting Value 70.0 dF STARTVAL
Staged Cooling
Total Number of Stages 2 STAGES
Stage 1 Time Guard Enable TG1
Stage 2 Time Guard Enable TG2
Stage 3 Time Guard Disable TG3
Heating PID
Proportional Gain 6.0 KP
Integral Gain 3.0 KI
Derivative Gain 5.0 KD
Starting Value 75.0 dF STARTVAL
Staged Heating
Total Number of Stages 2 STAGES
Stage 1 Time Guard Enable TG1
Stage 2 Time Guard Enable TG2
Stage 3 Time Guard Enable TG3
IAQ PID
Proportional Gain 0.1 KP
Integral Gain 0.0 KI
Derivative Gain 0.0 KD
Starting Value 0.0 %STARTVAL
Economizer PID (Not Used)
Proportional Gain -4.0 KP
Integral Gain -2.0 KI
Derivative Gain -3.0 KD
Starting Value 70.0 dF STARTVAL
Submaster Gain Limit -5.5 ESG
Submaster Center Value 60 %CTRVAL
Damper Movement Band
(Not Used)
0
% ECONBAND
OAT Temp Band (Not Used) 25 ^F TEMPBAND
Minimum Damper Position
(Not Used)
20
%MDP
Low Temp MDP Override
(Not Used)
100
%LOWMDP
DX Cooling Lockout On DXCTLO
DX Cooling Lockout Temp 45.0 dF DXLOCK
SAT CMP1 Lockout Temp 55.0 dF SATL01
SAT CMP2 Lockout Temp 50.0 dF SATL02
Time Guard Override Off TGO
Continuous Power Exhaust
(Not Used)
Disable
MODPE
Supply Fan Status Enable Disable SFSENABL
Max Offset Adjustment 2.0 ^F LIMT
Space Temp Trim 0.0 ^F RATTRIM
Supply Air Temp Trim 0.0 ^F SATTRIM