Specifications
13
SUPPLY AIR TEMPERATURE — HIGH LIMIT — The
Supply Air Temperature High Limit alarm is used to monitor
the value of the supply air temperature within a specified range.
If the supply air temperature becomes too high, an alarm condi-
tion will exist.
Supply Air
Temperature
High Limit: Display Units: Degrees F (Degrees C)
Display Range: –40.0 to 245.0
Default Value: 150.0
SUPPLY AIR TEMPERATURE — LOW LIMIT — The
Supply Air Temperature Low Limit alarm is used to monitor
the value of the supply air temperature within a specified range.
If the supply air temperature becomes too low, an alarm condi-
tion will exist.
Supply Air
Temperature
Low Limit: Display Units: Degrees F (Degrees C)
Display Range: –40.0 to 245.0
Default Value: 45.0
INDOOR AIR QUALITY ALERT LIMIT — The Indoor-
Air Quality Alert Limit alarm defines the allowable CO
2
levels
during occupied periods. If the CO
2
levels become too low or
too high during occupied periods, an alarm condition will exist.
Indoor Air Quality
Low Limit: Display Units: PPM (implied)
Display Range: 0.0 to 5000.0
Default Value: 0.0
Indoor Air Quality
High Limit Display Units: PPM (implied)
Display Range: 0.0 to 5000.0
Default Value: 1200.0
Table 7 — Alarm Service Configuration
Controller Identification Screen —
The controller
identification screen contains reference information used to
identify the PremierLink™ controller. See Table 8.
DESCRIPTION — The Description point displays the type of
device.
LOCATION — The Location point shows the location of the
device.
SOFTWARE PART NUMBER — The Software Part Num-
ber indicates the part number of the software being used.
MODEL NUMBER — The Model Number indicates the
model number of the device being used.
SERIAL NUMBER — The Serial Number indicates the serial
number of the device being used.
REFERENCE NUMBER — The Reference Number indi-
cates the version of the software being used.
Table 8 — Controller Identification
Holiday Configuration Screen —
The Holiday Con-
figuration screen is used by the PremierLink controller to store
configuration fields for up to twelve holidays. See Table 9.
START MONTH — The Start Month field is used to config-
ure the month that the holiday will start. The numbers 1
through 12 are used to indicate which month is specified.
Start Month: Range: 1 to 12
Default Value: 1 (January)
START DAY — The Start Day field is used to determine
which day the holiday will start.
Start Day: Range: 1 to 31
Default Value: 1
DURATION — The Duration field indicates how long the
holiday will last (in days).
Duration: Range: 0 to 365
Default Value: 0
As an example, if a Holiday is configured for Month 2,
Day 5, Duration 2, then the Holiday will start February 5 and
end February 7.
Table 9 — Holiday Configuration
Occupancy Configuration Screen —
The Occupan-
cy Configuration Screen is used to configure the occupancy
schedule for the PremierLink controller. See Table 10.
MANUAL OVERRIDE HOURS — The Manual Override
Hours point is used to command a timed override by entering
the number of hours the override will be in effect. If the occu-
pancy schedule is occupied when this number is downloaded,
the current occupancy period will be extended by the number
of hours downloaded.
If the current occupancy period is unoccupied when the
occupancy override is initiated, the mode will change to occu-
pied for the duration of the number of hours downloaded. If the
occupancy override is due to end after the start of the next
occupancy period, the mode will transition from occupancy
override to occupied without becoming unoccupied and the
occupancy override timer will be reset.
An active occupancy override or a pending occupancy
override may be canceled by downloading a zero to this
configuration. Once a number other than zero has been down-
loaded to this configuration, any subsequent downloads of any
value other than zero will be ignored by the controller.
Manual Override
Hours: Units: hours
Range: 0 to 4
Default Value: 0
DESCRIPTION VALUE UNITS NAME
Alarm Control
Alarm Routing Control 00000000 ALRMCNT
Realarm Time 0 min REALARM
Control Temp Hysteresis 5.0 ^F SPTHYS
Supply Air Temperature
Low Limit 45.0 dF LOWLIM
High Limit 150.0 dF HIGHLIM
IAQ High Alert Limit
Low Limit 0.0 LOWLIM
High Limit 1200.0 HIGHLIM
DESCRIPTION VALUE UNITS NAME
Description: Rooftop Control DevDesc
Location: Location
Software Part Number: CESR131269-01 PartNum
Model Number: ModelNum
Serial Number: 0002000001 SerialNo
Reference Number: Version 1.100 RefNum
DESCRIPTION VALUE UNITS NAME
Start Month 1 MONTH
Start Day 1 DAY
Duration 0 DURATION