Specifications
Slow Change Override — The control prevents the capacity
stages from being changed when the leaving fluid tempera-
ture is close to the set point (within an adjustable deadband)
and moving towards the set point.
Ramp Loading ( ) — Limits the rate of change of leav-
ing fluid temperature. If the unit is in a cooling mode and
configured for Ramp Loading, the control makes 2 compari-
sons before deciding to change stages of capacity. The con-
trol calculates a temperature difference between the control
point and leaving fluid temperature. If the difference is greater
than 4° F (2.2° C) and the rate of change (°F or °C per minute)
is less than the configured Cooling Ramp Loading value
( ), the control does not allow any changes to the
current stage of capacity.
Low Entering Fluid Temperature Unloading — When the
entering fluid temperature is below the control point, the con-
trol will attempt to remove 25% of the current stages being
used. If exactly 25% cannot be removed, the control re-
moves an amount greater than 25%, but no more than nec-
essary. The lowest stage will not be removed.
Low Discharge Superheat — If a circuit’s discharge super-
heat is less than 15° F (8.3° C), the control does not increase
the current capacity stage and the EXD is not opened any
further. If the discharge superheat is less than 10° F
(5.6° C) and decreasing, the EXD is closed 50 steps every
10 seconds. If the discharge superheat is less than
5° F (2.8° C) and decreasing, the circuit is unloaded every
30 seconds until the superheat is greater than 5° F
(2.8° C). The final capacity stage is not unloaded unless an
alarm condition exists. This override is ignored for the first
3 minutes after a compressor is started.
Low Saturated Suction Temperature — To avoid freezing
the cooler, the control will compare the circuit Saturated Suc-
tion temperature with a predetermined freeze point. For wa-
ter circuits, the freeze point is 28 F (−2.2 C). For brine cir-
cuits, the freeze point is 8° F (4.4° C) below the cooling set
point (lower of 2 cooling set points for dual configuration).
If the saturated suction temperature is below the freeze point,
the unit capacity is not allowed to increase. For brine cir-
cuits, the freeze point can be entered by pressing
and scrolling 12 items down. The control will use the Brine
Freeze Point value less 6°F (3.3°C) as the freeze point to
compare with the Saturated Suction temperature. The de-
fault for the Brine Freeze Point is 34 F (1.1 C) which means
the control will use 28 F (−2.2 C) as the freeze point. This
value is adjustable from −15 F to 34 F (−26.1 to 1.1 C). For
water (brine) circuits, if the Saturated Suction temperature
falls below 34 F (1.1 C) (the Brine Freeze Point), the unit
capacity will not increase. If the Saturated Suction tempera-
ture falls below 28 F (−2.2 C), the Brine Freeze Point minus
6° F (3.3° C), for 90 seconds, all loaders in the circuit are
turned off. If this condition continues for a total of 3 min-
utes, the circuit will shut down.
High Condensing Temperature Unloading — Every 10 sec-
onds the control checks for the conditions below. Loaders
will be cycled as needed to control the saturated condensing
temperature below the configured maximum condensing tem-
perature. Configured maximums are 154 F (67.8 C) for 30GX,
152 F (66.7 C) for 30HXA, and 122 F (50 C) for 30HXC
units. If a circuit’s saturated condensing temperature is more
than 12° F (6.7 C) below the maximum condensing tem-
perature, the circuit capacity is not allowed to increase. If
the saturated condensing temperature is more than 2° F
(1.1° C) above the maximum condensing temperature for
60 seconds, a loader is turned off. If the saturated condensing
temperature rises to more than 5° F (2.8° C) above the maxi-
mum condensing temperature during the 60 seconds, a loader
is turned off immediately. If all the loaders were already off,
the compressor is shut down and an alarm is generated.
MOP (Maximum Operating Pressure) Override — The con-
trol monitors saturated condensing and suction temperature
for each circuit as well as differential oil pressure. Based
on a configurable maximum operating set point (saturated
suction temperature), set maximum condensing tempera-
ture, and minimum differential oil pressure, the control may
reduce the number of capacity stages being used and/or may
lower the EXD position when system pressures approach the
set parameters.
Head Pressure Control
GENERAL — The microprocessor controls the condenser
fans (30GX) or analog water valve (30HXC) to maintain the
saturated condensing temperature to a configurable set point.
The fans are staged or speed varied (30GX) or water valve
controlled (30HX) based on each circuit’s saturated con-
densing temperature and compressor status. Water cooled units
(30HXC) operating at less than 70 F (21.1 C) for entering
condenser water require the use of head pressure control.
The chiller must be field configured for the options shown
in Table 4. Fan stage settings are shown in Table 5.
AIR COOLED UNITS (30GX) — See Fig. 5 for condenser
fan locations.
47
46
45
44
43
42
41
0 200 400 600 800 1000
TIME (SECONDS)
2 STARTS
3 STARTS
DEADBAND EXAMPLE
LWT (F)
MODIFIED
DEADBAND
STANDARD
DEADBAND
8
7
6
5
LWT (C)
LEGEND
LWT — Leaving Water
Temperature
Fig. 4 — Deadband Multiplier
8