Specifications
Table 14 —Test Function and Subfunction Directory
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
1 Circuit A Discrete Output
Circuit A Discrete Output
Loader A1
Relay is OFF
Loader A1
Relay is ON
Loader A2 Similarly, use to test remaining outputs. Press the
down arrow key or to turn an output off.
Minimum Load Valve A
Circuit A Oil Heater
A1 Mtr. Cooling Solenoid
A2 Mtr. Cooling Solenoid
Circuit A Oil Pump
Oil Solenoid A1
Oil Solenoid A2
NOTE: Output will display Relay is ABSENT when
not configured
2 Circuit B Discrete Outputs
Circuit B Discrete Outputs
Loader B1
Relay is OFF
Loader B1
Relay is ON
Loader B2 Similarly, use to test remaining outputs. Press the
down arrow key or to turn the output off.
Minimum Load Valve B
Circuit B Oil Heater
B1 Mtr. Cooling Solenoid
B2 Mtr. Cooling Solenoid
Circuit B Oil Pump
Oil Solenoid B1
Oil Solenoid B2
NOTE: Output will display Relay is ABSENT when
not configured
3 Unit Discrete Output
Unit Discrete Output
Fan 1
Relay is OFF
Fan 1
Relay is ON
Fan 2 Similarly use to test remaining outputs. Press the
down arrow key or to turn output off.
Fan 3
Fan 4
Fan 5 Energizes Circuit A fans for 30HXA units.
Fan 6 Energizes Circuit B fans for 30HXA units.
Cooler Pump
Condenser Pump
Cooler Heater
Alarm
Remote Alarm 1 Currently not supported.
26