Specifications
Table 10 — Status Function and Subfunction Directory
SUBFUNCTION KEYPAD ENTRY DISPLAY COMMENT
1 Alarms
Alarm : xx
Reset Alarms: 1 <ENTER>
All current alarms are displayed Use as needed
2 General Parameters GENERAL PARAMETERS
Displays LOCAL ON/OFF or CCN ON/OFF
Force/clear value with HSIO or CCN device.
Must be ON for CCN clock control.
Control Mode
Run Status
Off/On
Occupied ?
Yes/No
CCN Enable
Off/On
CCN Chiller Start/Stop
Start/Stop
Alarm State
Normal/Alarm
Current Alarm 1
x.xx
Current Alarm 2
x.xx
Current Alarm 3
x.xx
Current Alarm 4
x.xx
Current Alarm 5
x.xx
Active Demand Limit
xxx.x%
Percent Total Capacity
xxx.x%
Water/Brine Setpoint
xx.x dF
Control Point
xx.x dF
Entering Fluid Temperature
xx.x dF
Leaving Fluid Temperature
xx.x dF
Emergency Stop
Emstop
Minutes Left for Start
xx min
Heat-Cool Status
Heat/Cool
3 Circuit A Analog Values
CIRCUIT A ANALOG VALUES
Percentage of total circuit capacity
currently in use.
Percentage of Total Capacity value not in
an alarm or fault condition.
Total Capacity
xxx.x%
Available Capacity
xxx.x%
Discharge Pressure
xxx.x PSI
Suction Pressure
xxx.x PSI
A1 Oil Pressure Diff.
xxx.x PSI
A2 Oil Pressure Diff.
xxx.x PSI
A1 Oil Pressure
xxx.x PSI
A2 Oil Pressure
xxx.x PSI
Discharge Gas Temperature
xxx.x dF
A1 Motor Temperature
xxx.x dF
A2 Motor Temperature
xxx.x dF