Technical data

170
Features
Fan operation - With the fan speed selector, fan mode can be set either manually
or automatically. In the manual mode it is possible to select three fan speeds
(low/medium/high) according to personal preference. In the auto mode fan speed
is regulated by a microprocessor in the control, based to the temperature chosen.
Temperature selector - This is designed to maintain the temperature at the
desired level. The reference value at the centre of the range is 20°C. By turning
the knob towards the symbol (-) the temperature is reduced from the original
setting (minimum value is 10°C). By turning the knob towards the symbol (+),
the temperature is raised from the original setting (maximum value is 30°C).
Energy saving mode - This function is especially useful when air conditioning
at night or in rooms where the user is likely to be absent for a longer period
of time. In this case, pushing the button raises the temperature during cooling
by 4°C and lowers it during heating by 4°C.
Seasonal changeover
- Manual - Selection of heating/cooling is done manually by pushing the
button on the control.
- Centralised (only for type A control) - Centralised seasonal changeover is
possible in two ways:
- by a switch located on the central control panel that allows heating/cooling
mode changeover (to be provided by the installer).
- by a temperature sensor located in contact with the entering water pipe
- Automatic, based on air temperature (only for type B control) - The
automatic seasonal changeover allows automatic switching of the fan coil
operating mode to cooling or heating, depending on the temperature set
by the user and on the room temperature.
External contact - The control has a 230 V input that can be used as window
contact or presence detector. When such a signal is activated (presence of
line voltage on the terminal block contact) the control is set to OFF mode. As
a consequence, all outputs (fan, valves etc.) are disconnected, and only frost
protection is active, if switched ON by the appropriate dip-switch.
Frost-protection - This function keeps the temperature from dropping below
7°C in rooms not used for long periods of time.
Electronic thermostats:
The Carrier electronic thermostats are
designed to control and optimise the
operation of hydronic terminal fan coil
units. They exist in two versions that
match all terminal fan coil configurations:
Type A Type B
2-pipe x
2-pipe changeover x
2-pipe and electric heater x
2-pipe changeover and electric heater x
4-pipe x
Thermostats
ELECTRONIC THERMOSTATS
Controls