Technical data
170
Features
• Fan operation - With the fan speed selector, fan mode can be set either manually
or automatically. In the manual mode it is possible to select three fan speeds
(low/medium/high) according to personal preference. In the auto mode fan speed
is regulated by a microprocessor in the control, based to the temperature chosen.
• Temperature selector - This is designed to maintain the temperature at the
desired level. The reference value at the centre of the range is 20°C. By turning
the knob towards the symbol (-) the temperature is reduced from the original
setting (minimum value is 10°C). By turning the knob towards the symbol (+),
the temperature is raised from the original setting (maximum value is 30°C).
• Energy saving mode - This function is especially useful when air conditioning
at night or in rooms where the user is likely to be absent for a longer period
of time. In this case, pushing the button raises the temperature during cooling
by 4°C and lowers it during heating by 4°C.
• Seasonal changeover
- Manual - Selection of heating/cooling is done manually by pushing the
button on the control.
- Centralised (only for type A control) - Centralised seasonal changeover is
possible in two ways:
- by a switch located on the central control panel that allows heating/cooling
mode changeover (to be provided by the installer).
- by a temperature sensor located in contact with the entering water pipe
- Automatic, based on air temperature (only for type B control) - The
automatic seasonal changeover allows automatic switching of the fan coil
operating mode to cooling or heating, depending on the temperature set
by the user and on the room temperature.
• External contact - The control has a 230 V input that can be used as window
contact or presence detector. When such a signal is activated (presence of
line voltage on the terminal block contact) the control is set to OFF mode. As
a consequence, all outputs (fan, valves etc.) are disconnected, and only frost
protection is active, if switched ON by the appropriate dip-switch.
• Frost-protection - This function keeps the temperature from dropping below
7°C in rooms not used for long periods of time.
Electronic thermostats:
The Carrier electronic thermostats are
designed to control and optimise the
operation of hydronic terminal fan coil
units. They exist in two versions that
match all terminal fan coil configurations:
Type A Type B
2-pipe x
2-pipe changeover x
2-pipe and electric heater x
2-pipe changeover and electric heater x
4-pipe x