Specifications
41
13.3.1 - Duct installation examples (continued)
Case 2
For units 30RB 182-262 with two V-shaped air condensers.
1
1
1
1
1
Fan motor access hatches (provide a 700 x 700 mm hatch) for each single and dual duct
Solution 1
One separate duct per fan
Circuit A
EV11-EV12
Circuit B
EV21-EV22
Each fan discharge to the outside has its own duct.
Solution 2
Circuit A
One separate duct for the EV11 + EV12 fan pair
Circuit B
One separate duct for the EV21 + EV22 fan pair
Each fan pair discharge to the outside has its own duct.