Specifications

30

                
Cooling capacity* kW 163 173 193 227 258 293 328 359 391 418 447 506 596 652 704 758
Heating capacity* kW 43 42 58 56 89 99 112 122 135 142 154 174 204 223 242 262
Unit power input* kW 56 59 70 73 95 101 117 124 143 146 164 185 211 233 257 279
Energy efficiency ratio* kW/kW 2.93 2.92 2.75 3.12 2.71 2.90 2.79 2.89 2.74 2.85 2.73 2.73 2.82 2.80 2.74 2.71

Standard unit*** kg 1882 1974 2074 2092 2260 2853 3049 3092 3218 3755 3895 4063 5285 5484 6145 6315
Unit with options**** kg 2052 2154 2244 2282 2450 3083 3279 3342 3478 4045 4185 4373 5645 5833 6555 6745
Unit with options† kg 2302 2404 2484 2522 2690 3393 3589 3692 3818 4395 4585 4795 - - - -
 Plate heat exchangers
Water volume circuit A l 1.75 1.75 1.75 3.75 3.75 5.5 5.5 5.5 5.5 7.5 7.5 7.5 5.5 5.5 7.5 7.5
Water volume circuit B l 3.5 3.5 3.5 3.75 3.75 3.75 3.75 5.5 5.5 5.5 5.5 7.5 5.5 5.5 7.5 7.5
Water volume circuit C l - - - - - - - - - - - - 5.5 7.5 5.5 7.5
Max. water-side operating pressure kPa 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
 Cylindrical, male gas thread
Connection in 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
Outside diameter mm 60.3 60.3 60.3 60.3 60.3 60.3 60.3 60.3 60.3 60.3 60.3 60.3 60.3 60.3 60.3 60.3
* Nominal conditions:
Evaporatorenteringandleavingwatertemperature=12°C/7°C
Desuperheaterenteringandleavingwatertemperature=50°C/60°C
Outsideairtemperature=35°C
** Weights shown are a guideline only
*** Standard unit (with MCHX coils) and desuperheater option
**** Unit with option 15 + desuperheater
Unit with option 15 + desuperheater + hydronic module with high-pressure dual pump


This option permits the production of free hot water using
heat reclaim by desuperheating the compressor discharge
gases. The option is available for the whole 30RB range.
A plate heat exchanger is installed in series with the air con-
denser coils on the compressor discharge line of each circuit.
The control configuration for the desuperheater option is
factory assembled (see chapter 12.3.3 - Control configura-
tion).