Specifications

24

30RB option 118A 232 262 302 342 372 402 432 462 522
 kW 220 249 283 320 354 377 413 437 488
 kW 76 101 108 125 132 151 156 175 198

Unit with option 15 kg 2398 2580 3229 3429 3518 3658 4241 4381 4591
Unit with option 15 + dual-pump hydronic
module option kg 2638 2818 3539 3739 3868 3998 4591 4781 5011
Standard unit kg 2208 2390 2999 3199 3268 3398 3951 4091 4281

Circuit A kg 29 29 42.5 44 45.5 46 55 57 57
Circuit B kg 29 29 31 31 45.5 46 47 47 57
* Nominalconditions:evaporatorentering/leavingwatertemperature=12°C/7°C.Outdoorairtemperature=35°C
** Weight shown is a guideline only.


  
Entering water temperature at start-up °C 6.8 40
Leaving water temperature during operation °C 5 15
  
Outdoor ambient temperature °C 0 48
Available static pressure Pa 0 0
Ambient temperature (option 28) °C -20 48

  
Entering water temperature at start-up °C 6.8 40
Leaving water temperature during operation °C 5 26
  
Outdoor ambient operating temperature °C -25 20
Available static pressure Pa 0 0


1. Evaporator
2. Air condenser (coils)
3. Three-way valve
4. Compressor
5. Check valve
6. Refrigerant pump
7. Check valve
8. Expansion device (EXV)
The change-over between the cooling and free-cooling modes
is automatically controlled (it is possible to block the change-
over to free-cooling by reconfiguring the machine - see
Controls IOM). The configurable parameters permitting
change-over are the outside air temperature and the leaving
water temperature set-point. As soon as the temperature
difference LWT
stp
- OAT is above 8 K the current capacity in
cooling mode is calculated and compared with the theoretical
free-cooling capacity. This comparison authorizes/stops the
change-over to free-cooling.
After change-over to free-cooling all compressors are
stopped (the compressor functions are bypassed). As soon
as the valves open, the free-cooling pumps are started. This
change-over logic takes around 10 minutes. Taking this
timing into consideration only one change-over cooling -
free-cooling is authorized per hour.
If the capacity supplied in the free-cooling mode is insuffi-
cient (set-point not reached), the unit automatically
changes over to cooling mode.
To optimize operation in free-cooling mode we strongly
recommend to use the set-point offset function. This
favours the change-over to free-cooling and increases the
capacity in free-cooling mode.
4
6
5
3
8
3
6
1
2
2
4
5
8
7 7