Specifications

CL-10
23XL PIC II RAMP_DEM TABLE CONFIGURATION SHEET
23XL PIC II TEMP_CTL TABLE CONFIGURATION SHEE
T
DESCRIPTION RANGE UNITS DEFAULT VALUE
Pulldown Ramp Type:
Select: Temp=0, Load=1
0/1 1
Demand Limit + kW Ramp
Demand Limit Source
Select: Amps=0, kW=1
0/1 0
Motor Load Ramp % Min
5 to 20 10
Demand Limit Prop Band
3 to 15 % 10
Demand Limit At 20 mA
40 to 100 % 40
20 mA Demand Limit Opt
0/1 DSABLE/ENABLE DSABLE
Motor Rated Kilowatts
50 to 9999 kW 145
Demand Watts Interval
5 to 60 MIN 15
DESCRIPTION RANGE UNITS DEFAULT VALUE
Control Point
ECW Control Option
0/1 DSABLE/ENABLE DSABLE
Temp Pulldown Deg/Min
2 to 10 ˆF 3
Temperature Reset
RESET TYPE 1
Degrees Reset At 20 mA
–30 to 30 ˆF 10
RESET TYPE 2
Remote Temp (No Reset)
–40 to 245 DEG F 85
Remote Temp (Full Reset)
–40 to 245 DEG F 65
Degrees Reset
–30 to 30 ˆF 10
RESET TYPE 3
CHW Delta T (No Reset)
0 to 15 ˆF 10
CHW Delta T (Full Reset)
0 to 15 ˆF 0
Degrees Reset
–30 to 30 ˆF 5
Select/Enable Reset Type
0 to 3 0