Specifications
CL-6
23XL PIC II OPTIONS TABLE CONFIGURATION SHEET
DESCRIPTION RANGE UNITS DEFAULT VALUE
Auto Restart Option
0/1 DSABLE/ENABLE DSABLE
Remote Contacts Option
0/1 DSABLE/ENABLE DSABLE
Soft Stop Amps Threshold
40 to 100 % 100
Stall/Hot Gas Bypass
Stall Limit/HGBP Option
Select: Stall=0, HGBP=1
0/1 0
Min. Load Point (T1/P1)
Stall/HGBP Delta T1
0.5 to 20 ˆF 1.5
Stall/HGBP Delta P1
30 to 170 PSI 150
Full Load Point (T2/P2)
Stall/HGBP Delta T2
0.5 to 20 ˆF 4
Stall/HGBP Delta P2
30 to 250 PSI 200
Stall/HGBP Deadband
0.5 to 3 ˆF 1
Stall Protection
Stall Delta % Amps
5 to 20 % 10
Stall Time Period
7 to 10 MIN 8
Ice Build Control
Ice Build Option
0/1 DSABLE/ENABLE DSABLE
Ice Build Termination
0=Temp, 1=Contacts, 2=Both
0 to 2 0
Ice Build Recycle
0/1 DSABLE/ENABLE DSABLE
Refrigerant Leak Option
0/1 DSABLE/ENABLE DSABLE
Refrigerant Leak Alarm mA
4 to 20 mA 20
Head Pressure Reference
Delta P @ 0% (4 mA)
20-30 PSI 25
Delta P @ 100% (20 mA)
35-50 PSI 35
Minimum Output
0-100 % 0