Owner's Manual

OnGuard v1.1 Integration Carrier Proprietary and Confidential ©2022 Carrier.
for v8.0 or later systems All rights reserved.
2
Building Integration Platform (v1.11) (see the Building Integration Platform’s installation guide):
Building Integration Platform Service installed
OnGuard® Connector Service installed
Username, password, and port number for the Building Integration Platform
Network connectivity between the i-Vu® Pro Server, OnGuard® server, and Building Integration Platform
server
When upgrading to i-Vu® Pro v8.0
If you are running the OnGuard Integration with a pre-v8.0 version of i-Vu® Pro, perform the following steps
when you upgrade to i-Vu® Pro v8.0:
1 During the upgrade to i-Vu® Pro v8.0, choose to keep your existing add-ons. Add-on configurations will be
saved.
2 Uninstall Building Integration Platform (BIP) v1.10, following the instructions in the Building Integration
Platform Installation Manual.
3 Install BIP v1.11, following the instructions in the Building Integration Platform Installation Manual.
Running the OnGuard add-ons with i-Vu® Pro v8.0 or later
When running the OnGuard add-ons with i-Vu® Pro v8.0 or later, it may appear that your server is using more
memory than it should. This occurs because v8.0 uses a newer version of Java, and most of the memory it reports
as used is actually free.
If you would like to see a more accurate report of memory usage, perform the steps below on your i-Vu® Pro
server:
1 Go to the
i-Vu Pro<x.x>\bin\launchers folder.
2 Open the
i-Vu Pro server.launch file in Notepad.
3 Add this line: cjgreen.monitoredapp.config.gcimpl=-XX:+UseParallelGC
4 Save the file.
5 Open the
i-Vu Pro service.launch file in Notepad.
6 Add the same line of text as above, and save the file.
7 Restart
i-Vu Pro. Memory usage should now display as significantly lower.