Owner's Manual
Table Of Contents
OnGuard v1.1 Integration Carrier Proprietary and Confidential ©2022 Carrier.
for v8.0 or later systems All rights reserved.
13
To add OnGuard® Alarm Points to an equipment file:
Once the alarm-manager.logic-script and alarm-manager.logic symbol has been properly installed, OnGuard®
Alarm points can be appended to existing equipment files with appropriate reference names.
1 Export the current Zone Mapping JSON configuration file (see Exporting Zone Mapping section above) and
note where you download the onguardmapping.json file.
2 In Snap, open the equipment file that corresponds to the zone that you want to append the OnGuard® alarm
points to.
3 Select Tools>Scripts>alarm-manager to open a script editor.
4 Press the Execute button in the script editor to run the script which will bring up a file dialog. Navigate to the
onguardmapping.json file created in step 1.
5 Select the onguardmapping.json file and click
Open.
6 From the drop-down list of available zones, select the zone that corresponds to your equipment file and click
Ok. The Alarm Manager points are appended to the open equipment file.
7 Close the script editor.
NOTE If constructing an equipment file serving multiple zones, repeat steps 4 through 6 for different zone
selections on the same equipment file.
Setting up alarms from the i-Vu® Pro system to OnGuard
In order to send alarms from the i-Vu® Pro system to the OnGuard® system, a source must be defined in the
OnGuard® system to act as the originator of the alarms. There can be many sources defined for the i-Vu® Pro
system to use, and each source can be configured to transfer i-Vu® Pro alarms by category.
The i-Vu® Pro alarms notifications that are sent to OnGuard® are:
○ Alarm is generated
○ Alarm is acknowledged
○ Alarm point returned to normal
Setting up the alarm source
1 On the
Alarms tab, click System Select > i-Vu Pro to OnGuard.
2 Select the
OnGuard Source to configure.
3 Under the
Category column to the right, select each alarm category to enable for that source.
4 Next to each alarm category, specify when it should transfer alarms:
• Select
No to always transfer alarms regardless of the schedule.
• Select
Yes to only transfer alarms during the scheduled time range. See Setting up the alarm transfer
schedule (page
14) for more information.