Owner's Manual

OnGuard v1.1 Integration Carrier Proprietary and Confidential ©2022 Carrier.
for v8.0 or later systems All rights reserved.
13
To add OnGuar Alarm Points to an equipment file:
Once the alarm-manager.logic-script and alarm-manager.logic symbol has been properly installed, OnGuard®
Alarm points can be appended to existing equipment files with appropriate reference names.
1 Export the current Zone Mapping JSON configuration file (see Exporting Zone Mapping section above) and
note where you download the onguardmapping.json file.
2 In Snap, open the equipment file that corresponds to the zone that you want to append the OnGuard® alarm
points to.
3 Select Tools>Scripts>alarm-manager to open a script editor.
4 Press the Execute button in the script editor to run the script which will bring up a file dialog. Navigate to the
onguardmapping.json file created in step 1.
5 Select the onguardmapping.json file and click
Open.
6 From the drop-down list of available zones, select the zone that corresponds to your equipment file and click
Ok. The Alarm Manager points are appended to the open equipment file.
7 Close the script editor.
NOTE If constructing an equipment file serving multiple zones, repeat steps 4 through 6 for different zone
selections on the same equipment file.
Setting up alarms from the i-Vu® Pro system to OnGuard
In order to send alarms from the i-Vu® Pro system to the OnGuard® system, a source must be defined in the
OnGuard® system to act as the originator of the alarms. There can be many sources defined for the i-Vu® Pro
system to use, and each source can be configured to transfer i-Vu® Pro alarms by category.
The i-Vu® Pro alarms notifications that are sent to OnGuard® are:
Alarm is generated
Alarm is acknowledged
Alarm point returned to normal
Setting up the alarm source
1 On the
Alarms tab, click System Select > i-Vu Pro to OnGuard.
2 Select the
OnGuard Source to configure.
3 Under the
Category column to the right, select each alarm category to enable for that source.
4 Next to each alarm category, specify when it should transfer alarms:
Select
No to always transfer alarms regardless of the schedule.
Select
Yes to only transfer alarms during the scheduled time range. See Setting up the alarm transfer
schedule (page
14) for more information.