Integrated Alarm Management is an add-on that enables the exchange of alarms between the i-Vu® Pro system
and the OnGuard® system.
Setting up alarms from OnGuard to the i-Vu® Pro system
In order to send alarms from an OnGuard® system to the i-Vu® Pro system, you must define a mapping. The
mapping describes the OnGuard® event source and the destination microblock which re-generates the alarm for
the i-Vu® Pro system.
Adding an alarm mapping
1 On the
Alarms tab, click OnGuard to i-Vu Pro.
2 Click the
Edit Events button.
3 Click the
Add New Mapping button.
4 In the
Mapping Configuration panel, set the OnGuard Source:
a) Click the
Event Type slot, then select a type from the available choices.
b) With the
Event Sub Type slot now selected, select a sub-type.
5 In the
Mapping Configuration panel, specify if this mapping should Use Schedule:
No will always transfer alarms regardless of the schedule.
Yes will only transfer alarms during the scheduled time range. See Setting up the alarm transfer schedule
(page
14) for more information.
NOTES
To remove a mapping, click the
Delete ( ) button to the right of the mapping.
You can use an exported configuration to generate an equipment file containing your mapped alarm points.
See
Exporting Zone Mapping below. Alarm points will be given refnames as indicated in the Refname
Template below.
To add alarm points to an existing equipment file, locate the
i-Vu® Pro Destination section on the Mapping
Configuration panel to see the microblock refname template generated by the add-on. Use this template to
construct a refname to be used in the equipment file to map this point to a BV microblock. See the refname
template and example below.
RefnameTemplate: almbv_p<panel>_d<device>_type<type>_subtype<subtype>
All of the fields in <> above are numbers provided by the OnGuard system.
EXAMPLE: almbv_p1_d4_type4_subtype8
In this example, the alarm is from Panel 1, device 4, event type 4 (system), sub-event 8 (door forced open)
Setting up the Integrated Alarm Management add-on