Installation manual
High Wall Type
Installation Manual
–22–
EN
Procedure 2
Each time   button is pushed, indoor unit 
numbers in the control group change cyclically. 
Select the indoor unit to change settings for.
The fan of the selected unit runs and the louvers 
start swinging. The indoor unit can be confirmed for 
which to change settings.
Procedure 3
Specify CODE No. [   ] with temp. setup   / 
 buttons.
Procedure 4
Select SET DATA [   ] with timer time   / 
 buttons.
Procedure 5
Push   button. When the display changes from 
flashing to lit, the setup is completed.
• To change settings of another indoor unit, repeat 
from Procedure 
2.
• To change other settings of the selected indoor 
unit, repeat from Procedure 3.
Use   button to clear the settings. 
To make settings after   button was pushed, 
repeat from Procedure 
2.
Procedure 6
When settings have been completed, push   
button to determine the settings. 
When   button is pushed, “SETTING” flashes 
and then the display content disappears and the air 
conditioner enters the normal stop mode.
 (While “SETTING” is flashing, no operation of the 
remote control is accepted.)
 Filter sign setting
According to the installation condition, the lighting 
time of the filter sign (Notification of filter cleaning) 
can be changed.
Follow to the basic operation procedure
(1 → 2 → 3 → 4 → 5 → 6 ).
• For the CODE No. in Procedure 
3, specify [01].
• For the [Set data] in Procedure 4, select the SET 
DATA of filter sign lighting time from the following 
table.
 To secure better effect of heating
When it is difficult to obtain satisfactory heating due 
to installation place of the indoor unit or structure of 
the room, the detection temperature of heating can 
be raised. Also use a circulator or other device to 
circulate heat air near the ceiling.
Follow to the basic operation procedure
(
1 → 2 → 3 → 4 → 5 → 6 ).
• For the CODE No. in Procedure 3, specify [06].
• For the set data in Procedure 
4, select the SET 
DATA of shift value of detection temperature to 
be set up from the table below.
SET DATA Filter sign lighting time
0000 None
0001 150 H (Factory default)
0002 2500 H
0003 5000 H
0004 10000 H
SET DATA Detection temp shift value
0000 No shift
0001 +1.8 °F (+1 °C)
0002 +3.6 °F (+2 °C)
0003 +5.4 °F (+3 °C) (Factory default)
0004 +7.2 °F (+4 °C)
0005 +9.0 °F (+5 °C)
0006 +10.8 °F (+6 °C)
22-EN