Installation manual
High Wall Type
Installation Manual
–14–
EN
Tightening connection
CAUTION
• Do not apply excessive torque. Otherwise, the 
nut may crack depending on the conditions.
▼ Tightening torque of flare pipe connections
Pressure of R410A is higher than that of R22.
(Approx. 1.6 times) Therefore, using a torque 
wrench, tighten the flare pipe connecting sections 
which connect the indoor and outdoor units of the 
specified tightening torque.
Incorrect connections may cause not only a gas 
leak, but also a trouble of the refrigeration cycle.
Align the centres of the connecting pipes and 
tighten the flare nut as far as possible with your 
fingers. Then tighten the nut with a spanner and 
torque wrench as shown in the figure.
REQUIREMENT
Tightening with an excessive torque may crack the 
nut depending on installation conditions.
Tighten the nut within the specified tightening 
torque.
Piping with outdoor unit
• Shape of valve differs according to the outdoor 
unit.
For details of installation, refer to the Installation 
Manual of the outdoor unit.
 Leak check test, evacuation and 
other procedure
For leak check test, evacuation, addition of 
refrigerant, and gas leak check, refer to the 
Installation Manual attached to the outdoor unit.
REQUIREMENT
Do not supply power to the indoor unit until the leak 
check test and evacuation are completed. (If the 
indoor unit is powered on, the pulse motor valve is 
fully closed, which extends the time for vacuuming.)
Open the valve fully
Open the valve of the outdoor unit fully.
For details, refer to the Installation Manual attached 
to the outdoor unit.
Heat insulation
Heat insulation for the pipes should be done 
separately for the liquid side and gas side. Because 
both of the liquid and gas side pipes become a low 
temperature during cooling operation, sufficient 
heat insulation should be done to prevent 
condensation.
• Heat insulator with a heat resistance of 248 °F 
(120 °C) or more must be used for the gas side 
pipe.
• The pipe connection section of the indoor unit 
must be heat insulated securely and compactly 
with the attached heat insulator.
Unit: ft•lbs (N•m)
Outer dia. of copper pipe Tightening torque
1/4” (6.4 mm) 10 - 13 (14 - 18)
3/8” (9.5 mm) 24 - 31 (33 - 42)
1/2” (12.7 mm) 37 - 46 (50 - 62)
5/8” (15.9 mm) 50 - 60 (68 - 82)
Work using double spanner
Fix with vinyl tape
Heat insulator 
(attached)
Local side pipe
14-EN