Specifications

29
= ROM default setting. Text in ( ) = display text. Figures in [ ] are used when communicating with the bus.
VLT
®
Series 2000 Programming
408 Terminal 46 Output (TERMINAL 46 OUTPUT)
Value:
Unit Ready (UNIT READY) [0]
Unit Ready Remote Control (UNT RDY RCTL) [1]
Enabled not Warning (ENABLED no WR) [2]
Running (RUNNING) [3]
Running, no warning (RUNNING noWR) [4]
Running in range, no warning (RUNinRANGE) [5]
Speed = reference, no warning (RUN@REF noWR) [6]
Alarm (ALARM) [7]
Alarm or warning (ALARM or WARN) [8]
Current limit (CURRENT LIMIT) [9]
Out of frequency range (OUT FREQ RGE) [10]
Out of current range (OUT CURR RGE) [11]
Reversing (REVERSING) [12]
Pulse output 15 Hz - 1.5 kHz (PULSEOUT 1500) [13]
Pulse output 15 Hz - 3.0 kHz (PULSEOUT 3000) [14]
Pulse output 15 Hz - value par. 005 (PULSPAR005) [15]
Send/receive RS485 (CTS/RTS-RS485) [18]
Receive/send RS485 (CTS/RTS-RS485) [19]
Function:
Using this parameter you can choose between different
output signals. The output is an open collector output and
therefore a pull-up resistor must be connected to terminal
12 (+24 V).
Description:
For the pulse output the lowest output frequency is 15 Hz
and the highest output frequency is 5 Hz.
RS 485 send/receive control is used when the serial port is
connected to the RS 485 network via a RS 232/RS 485
adapter.
VLT
12
46
20
VLT
12
46
20
VLT
12
20
Connection example where the signal is active high:
Connection example where the signal is active low:
Connection example using RS 232/485 adapter:
12V
SND/RCV
I
max
= 40mA
Imp
min
= 600
Imp
min
= 600
I
max
= 30mA
I
max
= 40mA
Imp
min
= 600