VLT ® Series 2000 Table of Contents Specification Chart Page 2 Installation Safety Dimensions Cooling Wiring Quick Setup 4 5 7 8 10 Operation 11 Programming Group 0 -- Operation and Display Group 1 -- Load and Motor Group 2 -- Reference and Limits Group 3 -- Functions and Timers Group 4 -- Inputs and Outputs Group 5 -- Serial Data Interface Group 6 -- Service and Display 16 18 22 25 27 31 38 Appendix Motor Coil and Filter Options PI Regulation 41 42 Parameter Groups Factory Default Settings Cust
Installation; Safety The VLT® Series 2000 Adjustable Frequency Drive (AFD) contains dangerous voltages when connected to line voltage. Only a competent electrician should carry out the electrical installation. WARNING Improper installation of the motor or the AFD may cause equipment failure, serious injury or death. Follow this manual and local and national safety codes. VLT ® Series 2000 It is possible for the VLT to start upon application of AC power.
VLT ® Series 2000 Installation; Dimensions VLT 2010-2030 Single-phase, 220-240 V Three-phase, 208-240 V 4.3 (110) 3.5 (90) 0.21 (5.5) 0.29 (7.5) 7.1 (180) 0.43 (11) NOTE: Minimum space above and below the unit is 4 inches. Minimum space to the sides of the unit is 0 inches. 9.3 (235) 10.2 (260) VLT 2010-2030 with module Single-phase, 220-240 V Three-phase, 208-240 V 4.3 (110) 3.5 (90) 0.17 (4.5) 0.21 (5.5) 0.29 (7.5) 7.1 (180) NOTE: Minimum space above and below the unit is 4 inches.
VLT ® Series 2000 Installation; Dimensions VLT 2020-2050 Three-phase, 380-415/460 V VLT 2040-2050 Three-phase, 208-240 V 4.3 (110) 3.5 (90) 0.21 (5.5) 0.29 (7.5) 7.1 (180) 0.43 (11) NOTE: Minimum space above and below the unit is 4 inches. Minimum space to the sides of the unit is 0 inches. 13.2 (335) 14.2 (360) VLT 2020-2050 with module Three-phase, 380-415/460 V 4.3 (110) 3.5 (90) 6 0.17 (4.5) 0.21 (5.5) 0.29 (7.5) 7.1 (180) NOTE: Minimum space above and below the unit is 4 inches.
VLT ® Series 2000 Installation; Cooling Mechanical Installation Minimum Clearance 4 Inches (100 mm) The VLT Series 2000 is cooled by natural or forced air convection. Therefore air must be able to pass freely under and over the unit The VLT adjustable frequency drive must be mounted on a flat vertical surface. To enable the VLT to get rid of the cooling air, you must allow free air space both above and below the adjustable frequency drive.
VLT ® Series 2000 Installation; Wiring CAUTION: It is the responsibility of the user or the person installing the drive to provide proper grounding and branch circuit protection for incoming power and motor overload. National Electrical Codes (NEC) and local codes must be observed.
N L1 L2 L3 PE L3 L2 U V M LINE W 82 81 98 97 96 94 / 95 94 93 L3 92 L2 91 L1 RS 232 RXD RS 232 TXD A IN DIN3 DIN4 10V A IN 0UT +24V DIN1 DIN2 46 12 18 19 20 27 29 50 53 55 60 61 71 72 01 02 03 JOGGING (par. 405) START/STOP (par. 402) REVERSING (par.
VLT ® Series 2000 Installation; Quick Setup Quick Setup If you know how to operate the VLT Series and and are familiar with the menus and parameters, go directly to the How to Program section of this manual. If you are not familiar with the VLT Series Adjustable Frequency Drive refer first the Operation section of this manual. How to Program NOTE: If you use a brake module, you must program parameter 300. If you want local operation via the display keys you must program parameters 003 and 004.
VLT ® Series 2000 Operation All Danfoss VLT Series 2000 AC drives utilize the same control card throughout the entire HP range. The VLT control panel consists of a keyboard and a display. VLT Control Panel A 60 Hz 0000000000000060 USE±000000000015 Menu Data Alarm Jog Stop Reset + – On B C The keyboard is used for two purposes: local control and programming. The display communicates VLT, motor and application information to the operator. Located on the control panel is a red and green status LED.
VLT ® Series 2000 Operation Programming Keys Menu is used to enter MENU MODE from either DATA MODE or DISPLAY MODE. MENU is also used for entering a specific group of parameters. Data The + and – keys are used for scrolling through Groups, Parameters and Data Value selections. Additionally these keys are used for speed up and down when operating in Local mode. is used for entering DATA MODE or DISPLAY MODE from MENU MODE. DATA is also used to move the cursor in data values.
VLT ® Series 2000 Operation The parameter number consists of three digits as shown. Parameter Numbering The left digit indicates the Group, and the two digits at the right specify the parameter number in the specific Group. Moving through the Program After the first power up, the drive is in DISPLAY MODE. To program the VLT's various Groups, use the MENU key to enter the MENU GROUP MODE. To travel through the available Groups, use the + followed by the or – Menu key keys.
VLT ® Series 2000 Operation Operational Modes Display Mode Shows value and unit — Defines the display — Status, and source of control — 15.0 Hz FREQUENCY RUN OK LOCAL. 1 — Direction of rotation — Setup number Menu Mode 0.0 Hz Parameter number flashes — 0.. = Cursor flashes 0 . .OPERATION AND0DISPLAY 0000 — Parameter group — Name Parameter Mode Flashing parameter numbe — 0.
VLT ® Series 2000 Operation From any state Menu + The figure below shows how to switch between the different groups. Data From any state Display Mode 60 Hz Alarm Mode Stop Reset 0000000000000060 USE±000000000015 Menu Mode Menu Group + Group + Data – Alarm Jog Stop Reset Time Out 20 Sec. No Action – Data + 6 1 0 Menu + – 0 – Menu Menu On Fwd. Rev.
VLT® Series 2000 Programming Group 0 -- Operation and Display 002 Setup Copy ((MENU SET COPY) Value 000 Language (LANGUAGE) Value: ★ English (ENGLISH) German (DEUTSCH) French (FRANCAIS) Danish (DANSK) Function and Description: [0] [1] [2] [3] Determines the language of the display. You can choose between English, German, French and Danish.
VLT® Series 2000 Programming 010 Local Reference (LOC REFERE) Value: 004 Local Reference (LOCAL SPEE) Value: 0 to fMAX Function: You choose Local reference if you want to set the speed (frequency) via the control panel. Description of choice: To use this parameter you must choose Local with external stop or Local and remote in parameter 003. the output frequency of the adjustable frequency drive can be changed by means of the "+" and "–" keys. If the AC line is disconnected the value changes to 0.00.
VLT® Series 2000 Programming Group 1 -- Load and Motors 103 (continued) Description: 101 Speed Control (SPEED CONT) Value: Open loop (OPEN LOOP) ★ Slip comp. (SLIP COMP) Closed loop (CLOSED LOOP) Function: [0] [1] [2] You can choose among three different kinds of speed control: Open loop, Slip compensated and Closed loop. Description: Choose Slip compensation for normal operation , where the speed must be constant no matter what the load is.
VLT® Series 2000 Programming 107 Motor Current (MOTOR CURR) Value: 110 Start Compensation (START COMP) Value: IMAG (par. 108) - IVLT, MAX (par. 209) Function: 0.00 - 99 V/A Function: It is important to specify the rated motor current because it is used in part to calculate torque and thermal motor protection, (ETR), Description: The rated motor current, which can be seen from the motor nameplate, must be entered. This is also chosen in Quick Set Up Menu step 2.
VLT® Series 2000 Programming 112 Slip Compensation (SLIP COMP.) Value: 120 Control Range (CONTRL RAN) Value: 0.0 - 20 Hz Function: 0 to 100% Function: Slip Compensation increases the output frequency and voltage of the VLT adjustable frequency drive with an increasing load to compensate for the motor's increasing slip (loss). This achieves a load-independent speed. Description: Choose a value so that the speed remains constant when the load increases.
VLT® Series 2000 Programming 125 Feedback Factor (FEEDBACK F) Value: 0 to 500% Function: ★ 100% The feedback factor is used if the transmitter cannot be selected optimally for the scale range of the setpoint. Description of choice: This parameter is only used if the feedback signal in parameter 114 is not of a suitable level. If you choose 100% the feedback signal is not changed. ★ = ROM default setting. Text in ( ) = display text. Figures in [ ] are used when communicating with the bus.
VLT® Series 2000 Programming Group 2 -- References and Limits 203 Jog Frequency (JOG FREQUE) Value: 200 Frequency Range (FREQUE RANGE) Value: ★ 0 to 120 Hz 0 to 500 Hz Function: 0.0 to fMAX Function: [0] [1] Using this parameter you can set and thus limit the output frequency range of the VLT adjustable frequency drive. Description: ★10 Hz The jog frequency is the fixed output frequency at which the drive runs when the jog function is activated.
VLT® Series 2000 Programming 208 Digital Reference 4 (REF. 4 DIG) Value: 210 Warning: Low Frequency (LO FREQ. W) Value: ★ 0 % of fMAX - fMIN -100.00% - +100.00% Function: The digital speed references are generated internally in the unit and presented as a percentage of the difference between the fMAX and fMIN selected in parameters 201 and 202, added to fMIN.
VLT® Series 2000 Programming 216 Decel (ramp-down) Time (RAMP DOWN) Value: 0.1 to 800 sec. Function: ★5s Using this parameter you can record the required deceleration time from rated output frequency to 0 Hz. Description: The ramp-down time can be selected in the range 0.1-800 seconds. If the ramp-down time is too short the VLT's voltage limit becomes active, which will extend the rampdown time. Short ramp-down times will require a VLT unit with a brake function and installation of a brake resistor.
VLT® Series 2000 Programming Group 3 -- Functions and Timers 308 DC Brake Voltage (DC-BRK VOL) Value: 300 Brake Function (START FREQ) Value: ★ Not Applied (NOT APPLIED) Applied (APPLIED) Function: 0 to 50 V Function: [0] [1] Using this parameter you can inform the VLT adjustable frequency drive that a brake function and a brake resistor have been connected. Description: Choose Applied if you use a brake function and a brake resistor. 306 DC Braking Time (DC-BRAKE T) Value: 0 to 60 sec.
VLT® Series 2000 Programming 310 Trip Delay at Current Limit (TRIP DLY@C) Value: 0 to 60 secs. ★ Infinite at 61 Function: Using this parameter you can record how long the current limit may be active before trip. Description: Record the delay time. ∆! WARNING: If you choose Infinite, and your load is between 105% and 160%, trip may occur after a given interval.
VLT® Series 2000 Programming Group 4 -- Inputs and Outputs 402 Terminal 18 (TERMINAL 18 START) Value: ★ Start (START) Pulse Start (PRESS CONT.) No Function (NO FUNCTION) Speed Up (SPEED UP) Digital Reference Select (SPEED SELECT) Reversing (REVERSING) Reset and Start (RESET&START) Motor Coasting & Start (COASTING/START) Function: [0] [1] [2] [3] [4] [5] [6] [7] This parameter gives the motor various start signals.
VLT® Series 2000 Programming 404 Terminal 27 Stop (INPUT 27) Value: Motor Coasting Stop (MTR. COAST) Quick-Stop (Q-STOP) DC Braking (DC-BRAKE) ★ Reset and Motor Coasting (RST & COAST) Stop (STOP=PRESS) Reset and Start (RST & START) Speed Down (SPEED DOWN) Digital Reference Select (SPEED SELECT) Function: 405 Terminal 29 Jog (TERMINAL 29 JOG) Value: [0] [1] [2] [3] [4] [5] [6] [7] Using this parameter (terminal 27) you can give the motor various stop signals.
VLT® Series 2000 Programming Connection example where the signal is active high: 408 Terminal 46 Output (TERMINAL 46 OUTPUT) Value: Unit Ready (UNIT READY) ★ Unit Ready Remote Control (UNT RDY RCTL) Enabled not Warning (ENABLED no WR) Running (RUNNING) Running, no warning (RUNNING noWR) Running in range, no warning (RUNinRANGE) Speed = reference, no warning (RUN@REF noWR) Alarm (ALARM) Alarm or warning (ALARM or WARN) Current limit (CURRENT LIMIT) Out of frequency range (OUT FREQ RGE) Out of current range
VLT® Series 2000 Programming 409 Terminal 01 Relay Output (RELAY 01) Value: ★ Unit ready (UNIT READY) [0] Unit ready - remote control (UNT RDY RCTL) [1] Enabled no warning (ENABLED noWR) [2] Running (RUNNING) [3] Running, no warning (RUNNING noWR) [4] Running in range, no warning (RUNinRANGE) [5] Running on reference, no warn (RUN@REF noWR) [6] Alarm (ALARM) [7] Alarm or warning (ALARM or WARN) [8] Current limit (CURRENT LIMIT) [9] Out of frequency range (OUT FREQ RGE) [10] Out of current range (OUT CURR R
VLT® Series 2000 Programming Group 5 -- Serial Data Interface 501 Bits/Sec. Baud Rate (BAUD RATE) Value: 500 Address (ADDRESS) Value: 01 to 99 101 to 199 Function: (echo) ★ 01 Using this parameter you set the bus address for each VLT via the control panel. Howeve,r the first telegram after the voltage connection can change the bus address. This means that address change from the bus is no longer possible.
VLT® Series 2000 Programming 502 Data Read-Out (DATA READOUT) continued [15] Warning parameter messages: Frequency low re; parameter 210 value: 32768 Frequency high re; parameter 211 value: 16384 Current limit, re; power section value: 8192 Key blocked value: 2048 Motor overload value: 1024 Inverter overload value: 512 Outside frequency range value: 256 Current higher than par.
VLT® Series 2000 Programming When using Logical and Bus values in parameters 503-510, the digital control terminals are either dependent on or overruled by the bus commands. 507 Direction of Rotation (DIRECTION) Value: ★ Digital (DIGITAL) [0] Bus (BUS) [1] Logical and (AND) [2] Logical or (OR) [3] Description: In parameters 503 to 510 you can choose to control the VLT adjustable frequency drive via the control unit's terminals (digitally) and or via the bus.
VLT® Series 2000 Programming Group 5 -- Serial Data Interface Protocol: Using the serial RS 232 port (terminals 71 and 72) you can read and set parameters of the VLT adjustable frequency drive and issue reference and control commands. The serial port can be used for point to point communication between the VLT and a PC. Communication takes place by means of a protocol specified by Danfoss, and using the echo function (parameter 500) you can connect several VLT adjustable frequency drives.
VLT® Series 2000 Byte 1: Start byte, which in this case must be the character "<" (ASCII: 60). Byte 2 and 3: The two-digit address of the adjustable frequency drive. This address is also programmed in parameter 500. Sending to address 00 means transmission to all units connected to the bus. None of the units will reply, but they will carry out the command. Byte 4: Control parameter telling the drive what to do with the following data values.
VLT® Series 2000 Programming VLT Status The four control and status bytes are used to send control commands to the adjustable frequency drive when the telegram is sent from the master and to send status from the VLT to the master when the telegram is returned from the VLT adjustable frequency drive.
VLT® Series 2000 Programming VLT Control Commands OFF 1: Makes a normal ramp stop of the motor and opens the relay output of the VLT (relay off). OFF 2: Makes a motor coast and opens the relay output (relay off) OFF 3: Same as OFF 1, but the motor makes a quick-stop. Bit 10: This bit has to be 1, if any of the control commands should cause a reaction.
VLT® Series 2000 Programming Group 600 -- Service and Diagnostics 606 Total Operation Hours (TOTAL OP HRS) Description: See parameter 610. 607 Running Hours (RUNNING HRS) Description: See parameter 610. 608 Number of Power-ups (NO POWER) Description: See parameter 610. 609 Number of Over-temperature (NO OVERTE) Description: See parameter 610. 610 Number of Over-voltage (NO OVERVO) Description: In formation stored by the VLT adjustable frequency drive for later analysis.
VLT® Series 2000 Programming Status Messages RUN OK (LOCAL) UNIT READY (LOCAL) Unit is running on reference. Control card and power section are powered up and OK. When the adjustable frequency drive's output frequency is reduced more quickly than the motor speed (due to inertia) can be changed, the motor will act as a generator. It will send energy back to the VLT and as a result the intermediate circuit voltage will increase.
VLT® Series 2000 Programming Warning Messages Messages Caused by Consequence Reset CURRENT LIMIT Over load VLT decreases speed -- VOLTAGE HIGH Regenerative motor operation or supply voltage too high The power section of the VLT stops within 5 sec. --- VOLTAGE LOW Missing phase or low supply The power section of the VLT stops within 5 sec. -- INVERTER TIME Inverter overload At 98.
Appendix; Options Appendix VLT 2000/2000 PACK, Motor Coil and Filter Options 1Ø / 3Ø (1 x 220-240 V / 3 x 208-240 V) VLT 2010 VLT 2015 VLT 2020 VLT 2030 EMC and motor coil module IP20 1-phase 195H6523 195H6524 195H6524 195H6525 EMC and motor coil module IP20 3-phase 195H6522 195H6522 195H6522 195H6522 EMC-filter module, IP20 (VBG-4) Motor coil option, IP00 3Ø (3 x 208-240 V) VLT 2040 VLT 2050 195H6528 195H6510 195H6510 195H6510 195H6510 Motor coil option, IP10 (VGB-4) 195H6521 195H6521
Appendix; PI Regulation The following instructions will enable quick and easy setup of the PI regulation and associated parameter settings. Detailed information about each parameter can be found in the parameter section of this manual. Parameter 100: Set the load type. There are several choices in each group but variable torque medium or variable torque medium with AEO will suit most pumps or fans. Parameter 101: Select closed loop operation.
Appendix; PI Regulation Example: The set-point is 40%, and the min. speed is 50%. 1. Selecting a new set-point. Choose a value that will raise the set-point about 10% higher than the min. speed. New set-point = % min. speed x 1.1 = 55% 2. Setting parameter 125. Apply the same increase to this parameter. 100 x 1.1 = 110% Parameter 201: Set min. frequency if required. If you enter a min. speed you must observe the following: • When min. speed is used parameter 411 must be set to "proportional with min.
Appendix; PI Regulation External Setpoint For inverse control; modification of the setpoint and feedback signal is required. 12 Link Example: A transmitter has a 0-15 foot span equal to 0-20mA. The PID set-point must be set at 12 feet for inverse control. • Enter 20-0 mA in parameter 413. The normal signal in figure A is converted to an inverse signal as shown in figure B. Start/Stop Parameter 402 (start) 27 16 18 + 50 53 % mA 55 – 100 20 55 0 Figure A. 7.
Appendix; PI Regulation External Manual Control Over-ride It is often necessary to run the machine manually for maintenance reasons. Manual control can be carried out manually from the keypad of all the units. If remote control of the manual over-ride is required additional circuitry is necessary. For the VLT Series 3500 special parameters are available for external manual over-ride. Refer to the VLT Series 3500 instruction manual.
VLT SERIES 2000 PARAMETER GROUPS AND FACTORY DEFAULT SETTINGS OPERATION and DISPLAY: LOAD and MOTOR: REFERENCES and LIMITS: FUNCTIONS and TIMERS: INPUTS and OUTPUTS: SERIAL DATA INTERFACE: SERVICE and DIAGNOSTICS: 000 LANGUAGE SELECT S) ENGLISH 001 MENU SETUP SELECT S) SETUP 1 002 SETUP COPY DO NOT COPY 003 LOCAL REMOTE S) REMOTE 004 LOCAL REFERENCE S) 0 Hz 005 DISPLAY VALUE S) 1000 006 LOCAL RESET S) ENABLE 007 LOCAL START/STOP S) ENABLE 008 LOCAL REVERSING S) DISABLE 009 LOCAL JOGGING S) ENABLE 010
OPERATION & DISPLAY: LOAD & MOTOR: REFERENCES & LIMITS: FUNCTIONS & TIMERS: INPUTS & OUTPUTS: SERIAL DATA INTER.: SERVICE & DIAG.