Unit installation

Table 7 - System Wiring Colors and Connections
WALL
CONTROL MODULE CONTROL WALL CONTROL
WIRE
Term. Block Term. Block
Color Term. No. Term. ID
No, tD
J3-9 B Black J1-4 B
J3-8 G Green J1-3 G
J3-7 R Red J1-2 R
J3-6 Y Yellow J1-4 Y
Table 8 - Temperature/Ohm Relationship
Temp. (°F / °C) Ohms
30 / - I 34,480
32 / 0 32,680
34 / 1 30,760
36 / 2 29,220
38 / 3 27,470
40 / 4 26,020
42 / 6 24,680
44 / 7 23,320
46 / 8 22,070
48 / 9 20,910
50 / I 0 19,830
52 / 11 18,820
54/12 17,870
56/13 16,920
58 / 14 16,160
60/16 15,260
62 / 17 14,530
64 / 18 13,790
66 / 19 13,090
68 / 20 12,480
70 / 21 11,860
72 / 22 11,270
74 / 23 10,750
76 / 24 10,250
78 / 26 9,750
80 / 27 9,300
82 / 28 8,840
84 / 29 8,432
86 / 30 8,042
88 / 31 7,668
90 / 32 7,310
92 / 33 6,993
94 / 34 6,661
96 / 36 6,368
98 / 37 6,085
1O0 / 38 5,811
102 / 39 5,571
104 / 40 5,313
106 / 41 5,088
108 / 42 4,869
110 / 43 4,660
112 / 44 4,450
114 / 46 4,268
116/47 4,019
118/48 3,918
120 / 49 3,750
Table 9 - Factory Set Blower Connection
HIGH or LOW Speed
Control Main Electrical
Blower Wire Speed
Module Harness Cable
J1-6 Orange Orange High
No No
Blue + Cap Medium
Connection Connection
J1-4 Red Red Low
Table 10 - Modify Blower Connection
HIGH or MEDIUM Speed
Control Main Electrical
Module Harness Cable Blower Wire
J1-6 Orange Orange
J1-4 Red Blue
No No
Connection Connection Red + Cap
Speed
High
Medium /
Low
11