Phau Ntawv Qhia
Table Of Contents
- Installation Instructions
- Safety Considerations
- Introduction
- Heater Packages
- Installation
- Check Equipment
- Mount Unit
- Nuisance sweating may occur if the unit is installed in a high humidity environment with low airflow.
- Downflow Installation
- Horizontal Installation
- A07565
- Fig. 2 – Slope Coil Unit in Upflow Application
- Horizontal Right Conversion of Units with Slope Coils
- 1. Remove blower and coil access panels and fitting panel (Fig. 6).
- 2. Remove coil mounting screw securing coil assembly to right side casing flange.
- 3. Remove coil assembly.
- 4. Lay fan coil on its right side and reinstall coil assembly with condensate pan down (Fig. 5).
- 5. Attach coil to casing flange using previously removed coil mounting screw.
- 6. Make sure pan cap in fitting door is properly seated on fitting door to retain low air leak rating of the unit.
- 7. Add gaskets from kit.
- 8. Align holes with tubing connections and condensate pan connections. Reinstall access panels and fitting panel.
- 9. Make sure liquid and suction tube grommets are in place to prevent air leaks and cabinet sweating. Install grommets after brazing.
- Horizontal Right Conversion of Units with A-Coils
- 1. Remove blower and coil access panels (Fig. 6).
- 2. Remove metal clip securing fitting panel to condensate pan. Remove fitting panel.
- 3. Remove 2 snap-in clips securing A-coil in unit.
- 4. Slide coil and pan assembly out of unit.
- 5. Remove horizontal drain pan support bracket from coil support rail on left side of unit and reinstall on coil support rail on right side of unit (Fig. 8).
- 6. Convert air seal assembly for horizontal right.
- a. Remove air seal assembly from coil by removing 4 screws (Fig. 6).
- b. Remove air splitter (B) from coil seal assembly by removing 3 screws (Fig. 7 inset).
- c. Remove filler plate (A) and install air splitter (B) in place of filler plate.
- d. Install filler plate (A) as shown in horizontal right application.
- e. Remove condensate troughs (C) and install on opposite tube sheets.
- f. Install hose onto plastic spout.
- 7. Install horizontal pan on right side of coil assembly.
- 8. Slide coil assembly into casing. Be sure coil bracket on each corner of vertical pan engages coil support rails.
- 9. Reinstall 2 snap-in clips to correctly position and secure coil assembly in unit. Be sure clip with large offsets is used on right side of unit to secure horizontal pan.
- 10. Remove two oval fitting caps from left side of the coil, access panel, and fitting panel.
- 11. Remove insulation knockouts on right side of coil access panel.
- 12. Remove 2 oval coil access panel plugs and reinstall into holes on left side of coil access panel and fitting panel.
- 13. Install condensate pan fitting caps (from Step 10) in right side of coil door making sure that cap snaps and seats cleanly on back side of the coil door. Make sure no insulation interferes with seating of cap.
- 14. Reinstall access and fitting panels, aligning holes with tubing connections and condensate pan connections. Be sure to reinstall metal clip between fitting panel and vertical condensate pan.
- 15. Make sure liquid and suction tube grommets are in place to prevent air leaks and cabinet sweating.
- A07566
- Fig. 3 – Slope Coil in Horizontal Left Application (Factory Configuration)
- Fig. 4 – A-Coil in Horizontal Left Application (Factory Configuration)
- Fig. 5 – Conversion for Horizontal Right Applications - Slope Coil
- Fig. 6 – Conversion for Horizontal Right Applications - A-Coil
- Manufactured and Mobile Home Housing Applications
- 1. Secure the fan coil to the structure using field-supplied hardware.
- 2. Allow a minimum of 24" (610 mm) clearance from access panels.
- 3. Recommended method of securing for typical applications:
- a. If fan coil is away from wall, attach pipe strap to top of fan coil using no. 10 self-tapping screws. Angle strap down and away from back of fan coil, remove all slack, and fasten to wall stud of structure using 5/16" lag screws. Typical both side...
- b. If fan coil is against wall, secure fan coil to wall stud using 1/8" (3 mm) thick right-angle brackets. Attach brackets to fan coil using no. 10 self-tapping screws and to wall stud using 5/16" lag screws (Fig. 9).
- Fig. 7 – Removal of Brackets on Modular Unit
- Fig. 8 – Drain Pan Support Bracket
- Fig. 9 – Mobile Home or Manufactured Housing Applications
- Air Ducts
- Electrical Connections
- Line Voltage Connections
- 24V Control System
- Connection To Unit
- Fig. 10 – Wiring Layout Air Conditioning Unit (Cooling Only)
- Fig. 11 – Wiring Layout Air Conditioning Unit (Cooling and 1-Stage Heat)
- Fig. 12 – Wiring Layout Heat Pump Unit (Cooling and 2-Stage Heat with No Outdoor Thermostat)
- Fig. 13 – Wiring Layout Heat Pump Unit (Cooling and 2-Stage Heat for Manufactured Housing)
- Transformer Information
- Heater Staging
- Refrigerant Tubing Connection and Evacuation
- 1. Cut tubing to correct length.
- 2. Insert tube into sweat connection on unit until it bottoms.
- 3. Braze connection using silver bearing or non-silver bearing brazing materials. Do not use solder (materials which melt below 800° F / 427° C). Consult local code requirements.
- 4. Evacuate coil and tubing system to 500 microns using a deep vacuum method.
- Refrigerant Flow-Control Device
- Disassembly
- 1. Use an adjustable wrench with a backup adjustable wrench to loosen Item # 3 (TXV equalizer line).
- 2. For Item #4 - Cut the wire tie and remove the black insulation. Remove the band from around the TXV bulb.
- 3. Cut the wire tie that holds the TXV equalizer line and bulb from the aluminum vapor header tube.
- 4. Remove 2 screws from the TXV bracket. Remove the TXV from the coil unit.
- Assembly
- 1. Mount the TXV bracket and TXV with the 2 screws removed during disassembly.
- 2. Connect Items #1 and #2 (TXV outlet and inlet respectively) and use an adjustable wrench with a backup wrench to tighten each nut. Tighten to between 10 and 20 ft-lbs.
- 3. Connect Item #3 and use an adjustable wrench with a backup adjustable wrench to tighten the flare nut. Tighten to approximately 12 ft-lbs.
- 4. Item # 4 - Reconnect the TXV bulb with a clamp and reinstall insulation around the TXV bulb and vapor tube.
- Fig. 16 – Mechanical TXV Removal
- 5. Use a wire tie to mount the 1/8" TXV equalizer and bulb tubes to the vapor header tube. Make sure that there is insulation between the aluminum vapor tube and copper tube.
- 6. Leak test the TXV fittings, then evacuate and charge the system to the required subcooling per the outdoor unit rating plate.
- Disassembly
- Condensate Drains
- Accessories
- Sequence of Operation
- Start-up Procedures
- Care and Maintenance
- Fig. 22 – Shipping Screws
- Table 2 – Electric Heater Static Pressure Drop (in. wc)
- Table 3 – Airflow Performance (CFM) Wet
- 1. Airflow based upon dry coil at 230V with factory-approved filter and electric heater (2 element heater sizes 018 through 036, 3 element heater sizes 042 through 060).
- 2. To avoid potential for condensate blowing out of drain pan prior to making drain trap: Return static pressure must be less than 0.40 in. wc. Horizontal applications of 042 - 060 sizes must have supply static greater than 0.20 in. wc.
- 1. Airflow based upon dry coil at 230V with factory-approved filter and electric heater (2 element heater sizes 018 through 036, 3 element heater sizes 042 through 060).
- 2. To avoid potential for condensate blowing out of drain pan prior to making drain trap: Return static pressure must be less than 0.40 in. wc. Horizontal applications of 042 - 060 sizes must have supply static greater than 0.20 in. wc.
FJ4: Installation Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
10
Install traps in the condensate lines as close to the coil as possible.
(
Fig. 19). Make sure that the outlet of each trap is below its connection
to the condensate pan to prevent condensate from overflowing the drain
pan. Prime all traps, test for leaks, and insulate traps if located above a
living area. Condensate drain lines should be pitched downward at a
minimum slope of 1" (25 mm) for every 10' (3 m) of length. Consult
local codes for additional restrictions or precautions.
Accessories
Humidifier
Connect the humidifier and humidistat to the fan coil unit as shown in
Fig. 20 and Fig. 21. The cooling lockout relay is optional.
A03003
Fig. 19 – Condensate Drain
Sequence of Operation
Continuous Fan
Thermostat closes the R to G connection. G energizes the fan relay on
the PCB which completes the circuit to the indoor blower motor. When
G is de-energized, there is a 90-second delay before the relay opens.
A95294
Fig. 20 – Wiring Layout of Humidifier to Heat Pump
A95295
Fig. 21 – Wiring Layout of Humidifier to Fan Coil
with Electric Heat
Cooling Mode
Thermostat energizes R to G, R to Y, and R to O (heat pump only). G
energizes the fan relay on the PCB which completes the circuit to the
indoor blower motor. When G is de-energized, there is a 90-second delay
before the fan relay opens.
Heat Pump Heating with Auxiliary Electric Heat
Thermostat energizes R to G, R to Y, and R to W connections. G
energizes the fan relay on the PCB which completes the circuit to the
indoor blower motor. W energizes the electric heat relay(s) which
completes the circuit to the heater element(s). When W is de-energized,
the electric heat relay(s) open, turning off the heater elements. When G
is de-energized there is a 90-second delay before the fan relay opens.
Electric Heat or Emergency Heat Mode
Thermostat closes R to W connection. W energizes the electric heat
relay(s) which completes the circuit to the heater element(s). Blower
motor is energized through the normally-closed contacts on the fan relay.
When W is de-energized, the electric heat relay(s) opens.
Start-up Procedures
Refer to outdoor unit Installation Instructions for system start-up
instructions and refrigerant charging method details.
FILTER
ACCESS
PANEL
SECONDARY DRAIN WITH
APPROPRIATE TRAP REQUIRED
(USE FACTORY KIT OR
FIELD-SUPPLIED TRAP)
PRIMARY TRAP REQUIRED
(USE FACTORY KIT OR
FIELD-SUPPLIED TRAP OF
SUFFICIENT DEPTH.
STANDARD P-TRAPS ARE
NOT SUFFICIENT. SEE
FIGURE OF RECOMMENDED
CONDENSATE TRAP)
R
G
C
E
L
O
Y
THERMOSTAT
R
R
C
O
Y
G
C
W
2
W
2
W
2
W
3
E
FAN COIL
(CONTROL)
HEAT PUMP
(CONTROL)
RED
GRY
BRN
WHT
WHT
BLU
VIO
HUMIDISTAT
RELAY
FAN HUMIDIFIER
115V
M
CAUTION
!
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in poor unit performance
and/or product damage.
Never operate unit without a filter. Factory authorized filter kits may be
used when locating the filter inside the unit. For those applications
where access to an internal filter is impractical, a field-supplied filter
must be installed in the return air duct system.
R
G
W
Y
THERMOSTAT
R
G
W
2
W
3
E
C
FAN COIL
(CONTROL)
C
Y
AIR COND.
HUMIDISTAT
FAN HUMIDIFIER
115V
RED
GRY
WHT
WHT
BLU
VIO
BRN
M