Specifications

30
Table 3 — ICVC Display Data (cont)
EXAMPLE 15 — WSMCHLRE DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
5. Scroll down to highlight .
NOTE: All variables with CAPITAL LETTER point names are avail-
able for CCN read operation; forcing shall not be supported on main-
tenance screens.
EXAMPLE 16 — NET_OPT DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
5. Scroll down to highlight .
NOTE: No variables are available for CCN read or write operation.
MENU
SERVICE
CONTROL ALGORITHM STATUS
SELECT
WSMDEFME
DESCRIPTION STATUS UNITS POINT
WSM Active? 0/1 NO/YES WSMSTAT
Chilled Water Temp 0.0-99.9 ° F (°C) CHWTEMP
Equipment Status 0/1 OFF/ON CHWRST
Commanded State TEXT CHWRENA
CHW Setpoint Reset Value 0.0-25.0 ^ F (^C) CHWRVAL
Current CHW Set Point 0.0-99.9 ° F (°C) CHWSTPT
MENU
SERVICE
EQUIPMENT CONFIGURATION
SELECT
NET_OPT
DESCRIPTION STATUS UNITS POINT DEFAULT
Loadshed Function
Group Number 1-16 LDSGRPN 0
Demand Limit Decrease 0-60 % LDSDLTA 20
Maximum Loadshed Time 30-480 MIN MAXSHED 120
CCN Occupancy Config:
Schedule Number 3-99 OCC_NUM 3
Broadcast Option 0-1 DSABLE/ENABLE OCCBRCST DSABLE
Alarm Configuration
Re-Alarm Time 0-1440 MIN RETIME 30
Alarm Routing 0-1 ROUTING 10000000