Specifications
26
Table 3 — ICVC Display Data (cont)
EXAMPLE 7 — VFD
VFD_STAT SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation.
EXAMPLE 8 — ICVC PWD
To access this display from the ICVC default screen:
1. Press .
2. Press
3. Scroll down to highlight .
NOTE: The Disable Service Password parameter supports the service tool password disable access. It will only allow forcing with the service tool
for a one time bypass of both the service menu and the VFD config data table. Exit from the service menu reverts to normal password operation.
Those with (**) shall support write operations for ICVC only.
The Reset Alarm? and CCN mode? parameters support write operations from CCN and LEI devices when the Remote Reset Option is enabled.
DESCRIPTION STATUS UNITS POINT
VFD Fault Code 0-272 VFD_FLT
Single Cycle Dropout 0-1 NORMAL/ALARM CYCLE_1
Line Current Imbalance 0-1 NORMAL/ALARM LINEIM_I
Line Voltage Imbalance 0-1 NORMAL/ALARM LINEIM_V
Line Phase Reversal 0-1 NORMAL/ALARM PH_REV
High Line Voltage 0-1 NORMAL/ALARM HI_VOLT
Low Line Voltage 0-1 NORMAL/ALARM LOW_VOLT
High DC Bus Voltage 0-1 NORMAL/ALARM HI_DCBUS
Low DC Bus Voltage 0-1 NORMAL/ALARM LO_DCBUS
Motor Current Imbalance 0-1 NORMAL/ALARM MOTIM_I
Motor Overload 0-1 NORMAL/ALARM MOTOR_OV
Rectifier Overcurrent 0-1 NORMAL/ALARM RECT_OI
Rectifier Overtemp 0-1 NORMAL/ALARM RECT_OT
Rectifier Power Fault 0-1 NORMAL/ALARM RECT_PU
Inverter Overcurrent 0-1 NORMAL/ALARM INV_OI
Inverter Overtemp 0-1 NORMAL/ALARM INV_OT
Inverter Power Fault 0-1 NORMAL/ALARM INV_PU
Ground Fault 0-1 NORMAL/ALARM GRND_FLT
Frequency Fault 0-1 NORMAL/ALARM FREQFLT
VFD Power on Reset 0-1 NORMAL/ALARM VFD_POR
Start Complete 0-1 FALSE/TRUE START_OK
Stop Complete 0-1 FALSE/TRUE STOP_OK
Condenser High Pressure 0-1 NORMAL/ALARM PRS_TRIP
Motor Amps Not Sensed 0-1 NORMAL/ALARM NO_AMPS
Start Acceleration Fault 0-1 NORMAL/ALARM ACCELFLT
Stop Fault 0-1 NORMAL/ALARM AMPSTOP
VFD Start Inhibit 0-1 NORMAL/ALARM STRT_INH
VFD Checksum Error 0-1 NORMAL/ALARM CHECKSUM
VFD Comm Fault 0-1 NORMAL/ALARM VFD_COMM
VFD Fault 0-1 NORMAL/ALARM VFDFAULT
VFD Gateway Version # 0-255 VFG_VER
VFD Inverter Version # 0-1000 INV_VER
VFD Rectifier Version # 0-1000 REC_VER
MENU
STATUS
VFD_STAT
SELECT
DESCRIPTION STATUS UNITS POINT
Disable Service Password 0-1
DS/ENABLE PSWD_DIS
**Remote Reset Option 0-1 DS/ENABLE RESETOPT
Reset Alarm ? 0-1 NO/YES REMRESET
CCN Mode ? 0-1 NO/YES REM_CCN
MENU
STATUS
ICVC_PWD