Specifications

24
Table 3 — ICVC Display Data (cont)
EXAMPLE 4 — COMPRESS DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation;
those with (**) shall support write operations for ICVC only.
EXAMPLE 5 — HEAT_EX DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation;
those with (**) shall support write operations for ICVC only.
MENU
STATUS
COMPRESS
SELECT
DESCRIPTION STATUS UNITS POINT
Actual VFD Speed 0-115 % VFD_ACT
Compressor Motor RPM 0-300000 RPM CPR_RPM
Compressor Motor Frequency 0-10000 Hz VFD_FREQ
Compressor Maximum Speed 0-101 Hz MAXSPEED
Compressor Minimum Speed 0-100 % MINSPEED
VFD Delta –2-2 % VFDDELTA
**Target VFD Speed 0-100 % VFD_TRG
VFD Speed Output 0-100 % VFD_OUT
Oil Pump Relay 0/1 OFF/ON OILR
**Oil Pressure Delta P –6.7-420 PSI (kPa) OILPD
Oil Sump Temp –40-245 ° F (° C) OILT
Vaporizer Temperature –40-245 ° F (° C) VAP_TEMP
Oil Heater Relay 0/1 OFF/ON OILHEAT
Vaporizer Heater 0/1 OFF/ON VAP_HEAT
Comp Motor Winding Temp –40-245 ° F (° C) MTRW
Comp Discharge Temp –40-245 ° F (° C) CMPD
Discharge Superheat –20-999 ^F (^C) SUPRHEAT
Stall Protection Counts 0-5 SPC
Spare Temperature 1 –40-245 ° F (° C) SPARE_T1
Spare Temperature 2 –40-245 ° F (° C) SPARE_T2
MENU
STATUS
HEAT_EX
SELECT
DESCRIPTION STATUS UNITS POINT
**Chilled Liquid Delta P –6.7-420 PSI (kPa) CHLPD
Entering Chilled Liquid –40-245 ° F (° C) ECL
Leaving Chilled Liquid –40-245 ° F (° C) LCL
Chilled Liquid Delta T –40-245 ^F (^C) CHL_DT
Chill Liq Pulldown/Min –20-20 ^F (^C) CHL_PULL
Calc Evap Sat Temp –40-245 ° F (° C) ERT
**Evaporator Pressure –6.7-420 PSI (kPa) ERP
Evap Refrig Liquid Temp –40-245 ° F (° C) EST
Evaporator Approach 0-99 ^F (^C) EVAP_APP
**Condenser Liquid Delta P –6.7-420 PSI (kPa) CDLPD
Entering Cond Liquid –40-245 ° F (° C) ECDL
Leaving Cond Liquid –40-245 ° F (° C) LCDL
Condenser Refrig Temp –40-245 ° F (° C) CRT
**Condenser Pressure –6.7-420 PSI (kPa) CRP
Condenser Approach 0-99 ^F (^C) COND_APP
Vaporizer Temp –40-245 ° F (° C) VAP_TEMP
Reclaim Delta T –500-500 ^F (^C) R_DELTA
Oil Reclaim Output 0-100 % OIL_MA
VFD Coolant Flow 0-100 % VFD_FOUT
Hot Gas Bypass Relay 0/1 OFF/ON HGBYPASS
Active Delta P 0-200 PSI (kPa) DP_A
Active Delta T 0-200 ^F (^C) DT_A
HGBP Delta T 0-200 ^F (^C) DT_C
Head Pressure Reference 0-100 % HPR