Specifications

23
Table 3 — ICVC Display Data (cont)
EXAMPLE 2 — MAINTSTAT DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press ( will be highlighted).
3. Press .
NOTES:
1. Numbers in parentheses indicate the equivalent CCN BEST++™ programming LEI or BACnet Translator use.
2. Off (0), Local (1), CCN (2), Reset (3)
3. Timeout (0), Ready (1), Recycle (2), Startup (3), Running (4), Demand (5), Ramping (6), Auto Restart (7), Override (8), Tripout (9), Control Test
(10), Lockout (11), Pumpdown (12), Prestart (13)
4. Normal (0), Alert (1), Alarm (2).
5. All variables with capital letter point names are available for CCN read operation.
Those shown with (*) support write operations for all CCN and LEI devices.
Those shown with (†) shall support one time write operations for the ICVC only when the value is initially zero.
Those shown with (**) shall support write operations for the ICVC only.
EXAMPLE 3 — STARTUP DISPLAY SCREEN
To access this display from the ICVC default screen:
1. Press .
2. Press .
3. Scroll down to highlight .
4. Press .
NOTE: All variables with CAPITAL LETTER point names are available for CCN read operation.
Those shown with (**) shall support write operations for the ICVC only.
MENU
STATUS
MAINSTAT
SELECT
DESCRIPTION STATUS UNITS POINT
Control Mode NOTE 2 NOTE 2 MODE
Run Status NOTE 3 NOTE 3 STATUS
Start Inhibit Timer 0-15 min T_START
Occupied ? 0/1 NO/YES OCC
System Alert/Alarm 0-2 NOTE 4 SYS_ALM
*Chiller Start/Stop 0/1 STOP/START CHIL_S_S
*Remote Start Contact 0/1 OPEN/CLOSE REMCON
Temperature Reset –30-30 ^ F (^ C) T_RESET
*Control Point 10-65 ° F (° C) LCW_STPT
Chilled Liquid Temp –40-245 ° F (° C) CHL_TMP
*Active Demand Limit 40-100 % DEM_LIM
Percent Line Current 0.0-9999 % LN AMPS_P
Percent Line Kilowatts 0.0-9999 % LINE KW_P
Auto Demand Limit Input 4-20 mA AUTODEM
Auto Chilled Liq Reset 4-20 mA AUTORES
Remote Reset Sensor –40-245 ° F (°C) R_RESET
†Total Compressor Starts 0-99999 C_STARTS
Starts in 12 Hours 0-8 STARTS
†Compressor Ontime 0-500000.0 HOURS C_HRS
**Service Ontime 0-32767.0 HOURS S_HRS
Ice Build Contact 0/1 OPEN/CLOSE ICE_CON
Refrigerant Leak Sensor PPM 0.0-9999.0 mA REF_LEAK
Emergency Stop 0/1 ENABLE/EMSTOP EMSTOP
MENU
STATUS
STARTUP
SELECT
DESCRIPTION STATUS UNITS POINT
**Chilled Liquid Pump 0-1 OFF/ON CHLP
Chilled Liquid Flow 0-1 NO/YES CHL_FLOW
**Condenser Liquid Pump 0-1 OFF/ON CDP
Condenser Liquid Flow 0-1 NO/YES CDL_FLOW
Oil Pump Relay 0-1 OFF/ON OILR
Oil Reclaim Output 0-100.0 %(4 to 20mA) OIL_MA
**Oil Pressure Delta P –6.7-200 PSI (kPa) OILPD
Oil Sump Temp –40.0-245.0 ° F (° C) OILT
Vaporizer Temp –40.0-245.0 ° F (° C) VAP_TEMP
VFD Start 0-1 NO/YES VFDSTART
Start Complete 0-1 FALSE/TRUE START_OK
Stop Complete 0-1 FALSE/TRUE STOP_OK
VFD Speed Output 0.0-100.0 % VFD_OUT
Comp Motor RPM 0-300000 RPM CPR_RPM
Comp Motor Frequency 0-10000 Hz VFD_FREQ
Comp Maximum Speed 0-101 Hz MAXSPEED
Comp Minimum Speed 0-100 % MINSPEED
**Tower Fan Relay Low 0-1 OFF/ON TFR_LOW
**Tower Fan Relay High 0-1 OFF/ON TFR_HIGH
Spare Safety Input 0-1 ALARM/NORMAL SAFETY
Shunt Trip Relay 0-1 OFF/ON TRIPR