Specifications
17
2. Press or to highlight the desired
status table. The list of tables is:
•MAINSTAT — Overall chiller status
•STARTUP — Status required to perform start-up of
chiller
•COMPRESS — Status of sensors related to the com-
pressor
•HEAT_EX — Status of sensors related to the heat
exchangers
•POWER — Status of motor input power
•VFD_STAT — Status of the variable frequency drive
•ICVC_PSWD — Service menu password forcing
access screen
3. Press to view the desired point status table.
4. On the point status table, press or
until the desired point is displayed on the
screen.
OVERRIDE OPERATIONS
To Override a Value or Status
1. From any point status screen, press or
to highlight the desired value.
2. Press to select the highlighted value. Then:
For Discrete Points — Press or to
select the desired state.
For Analog Points — Press or
to select the desired value.
3. Press to register the new value.
NOTE: When overriding or changing metric values, it is nec-
essary to hold down the softkey for a few seconds in order to
see a value change, especially on kilopascal values.
To Remove an Override
1. On the point status table press or
to highlight the desired value.
2. Press to access the highlighted value.
3. Press to remove the override and return
the point to the PIC III’s automatic control.
Override Indication
— An override value is indicated by
“SUPVSR,” “SERVC,” or “BEST” flashing next to the point
value on the STATUS table.
NEXT
PREVIOUS
SELECT
NEXT
PREVIOUS
NEXT
PREVIOUS
SELECT
YES
NO
YES NO
ENTER
EXIT
INCREASE
DECREASE
ENTER
NEXT
PREVIOUS
SELECT
RELEASE