Specifications
CL-11
23XRV PIC III RAMP_DEM TABLE CONFIGURATION SHEET
23XRV PIC III TEMP_CTL TABLE CONFIGURATION SHEET
DESCRIPTION RANGE UNITS DEFAULT VALUE
Pulldown Ramp Type:
Select: Temp=0, kW=1
0/1 1
Demand Limit and kW Ramp
Demand Limit Source
Select: Amps=0, kW=1
0/1 0
Amps or kW Ramp % Min 5 to 20 10
Demand Limit Prop Band 3 to 15 % 10
Demand Limit At 20 mA 40 to 100 % 40
20 mA Demand Limit Opt 0/1 DSABLE/ENABLE DSABLE
Demand Watts Interval 5 to 60 MIN 15
DESCRIPTION RANGE UNITS DEFAULT VALUE
Control Point Source
ECL Control Option 0/1 DSABLE/ENABLE DSABLE
Temp Pulldown Ramp/Min
2 to 10
(1.1 to 5.6)
ˆF
(ˆC)
3
(1.7)
Temp er a t ure R eset
RESET TYPE 1
Degrees Reset At 20 mA
–30 to 30
(–17 to 17)
ˆF
(ˆC)
10
(6)
RESET TYPE 2
Remote Temp (– > No Reset)
–40 to 245
(–40 to 118)
° F
(° C)
85
(29)
Remote Temp (– > Full Reset)
–40 to 245
(–40 to 118)
° F
(° C)
65
(18)
Degrees Reset
–30 to 30
(–17 to 17)
ˆF
(ˆC)
10
(6)
RESET TYPE 3
CHL Delta T (– > No Reset)
0 to 15
(0 to 8)
ˆF
(ˆC)
10
(6)
CHL Delta T (– > Full Reset)
0 to 15
(0 to 8)
ˆF
(ˆC)
0
(0)
Degrees Reset
–30 to 30
(–17 to 17)
ˆF
(ˆC)
5
(3)
Enable Reset Type 0 to 3 0