Specifications

CL-7
23XRV PIC III OPTIONS TABLE CONFIGURATION SHEET
DESCRIPTION RANGE UNITS DEFAULT VALUE
Auto Restart Option 0/1 DSABLE/ENABLE DSABLE
Remote Contacts Option 0/1 DSABLE/ENABLE DSABLE
Soft Stop Amps Threshold 40 to 100 % 100
Hot Gas Bypass
HGBP Option 0,1,2 0=DSABLE
1=HGBP
2=LOW LOAD HGBP
0=DSABLE
Min. Load Point (T1, P1)
HGBP Delta T1
0.5 to 20
(.3 to 11.1)
ˆF
(ˆC)
1.5
(.8)
HGBP Delta P1
10 to 170
(68.9 to 1172.2)
PSI
(kPa)
150
(1034.2)
Full Load Point (T2, P2)
HGBP Delta T2
0.5 to 20
(.3 to 11.1)
ˆF
(ˆC)
4
(2.2)
HGBP Delta P2
30 to 250
(206.9 to 1724)
PSI
(kPa)
200
(1379)
HGBP Deadband 0.5 to 3
(.3 to 1.7)
ˆF
(ˆC)
1
(.6)
HGBP On Delta T 0.5-10 (0.3-5.6) ^F (^C) 2.0 (1.1)
HGBP Off Delta T 1.0-10 (0.6-5.6) ^F (^C) 4.0 (2.2)
Stall Protection
Stall Delta % Amps 5 to 20 % 10
Stall Time Period 7 to 10 MIN 8
Ice Build Control
Ice Build Option 0/1 DSABLE/ENABLE DSABLE
Ice Build Termination 0-2 0
(0=TEMP, 1=Contact, 2=Both)
Ice Build Recycle 0/1 DSABLE/ENABLE DSABLE
Refrigerant Leak Option 0/1 DSABLE/ENABLE DSABLE
PPM at 20 mA 0-99999 1000
Refrigerant Leak Alarm PPM 0-99999 500
Head Pressure Reference
Delta P at 0% (4 mA)
20-85
(138-586)
PSI
(kPa)
25
(172)
Delta P at 100% (20 mA)
20-85
(138-586)
PSI
(kPa)
50
(345)
Minimum Output 0 to 100 % 0