23XRV PIC III VFD_CONF TABLE CONFIGURATION SHEET
DESCRIPTION RANGE UNITS DEFAULT VALUE
Motor Nameplate Voltage 480-480 VOLTS 480
Compressor 100% Speed 54-101 Hz 70
Rated Line Voltage 346-480 VOLTS 460
Rated Line Amps 10-5000 AMPS 200
Rated Line Kilowatts 0-999999 KW 100
Motor Rated Load KW 0-999999 KW 100
Motor Rated Load Amps 10-5000 AMPS 200
Motor Nameplate Amps 10-5000 AMPS 100
Motor Nameplate RPM 1500-3030 2672
Motor Nameplate KW 0-999999 KW 100
Inverter PWM Frequency
(0=4 k Hz, 1=2 k Hz)
0/1 0
Skip Frequency 1 0.0-102 Hz 102
Skip Frequency 2 0.0-102 Hz 102
Skip Frequency 3 0.0-102 Hz 102
Skip Frequency Band 0.0-102 Hz 0
Line Voltage % Imbalance 1-10 % 10
Line Volt Imbalance Time 1-10 SEC 10
Line Current % Imbalance 5-40 % 40
Line Current Imbal Time 1-10 SEC 10
Motor Current % Imbalance 5-40 % 40
Motor Current Imbal Time 1-10 SEC 10
Increase Ramp Time 5-60 SEC 30
Decrease Ramp Time 5-60 SEC 30
Single Cycle Dropout 0/1 DSABLE/ENABLE DSABLE