Specifications
CL-3
Start Liquid Pumps and Establish Liquid Flow
Oil Level OK and Oil Temperature OK Oil Pressure
Restart Compressor, Bring Up To Speed. Shut Down. Any Abnormal Coastdown Noise? Yes* No
*If yes, determine cause.
START MACHINE AND OPERATE. COMPLETE THE FOLLOWING:
A: Trim charge and record under Charge Refrigerant Into Chiller section on page 63.
B: Complete any remaining control calibration and record under Controls section (pages 12-46).
C: Take at least two sets of operational log readings and record.
D: After machine has been successfully run and set up, shut down and mark shutdown oil levels.
E: Give operating instructions to owner’s operating personnel. Hours Given:
Hours
F: Call your Carrier factory representative to report chiller start-up.
G: Register LiquiFlo2 VFD start up on www.automation.rockwell.com/complete1/warp.
H: Return a copy of this completed checklist to the local Carrier Service office.
SIGNATURES:
CARRIER
TECHNICIAN
DATE
CUSTOMER
REPRESENTATIVE
DATE