APPENDIX C — OPTIONAL BACNET COMMUNICATIONS WIRING (cont)
Table G — Network Points List (cont)
LEGEND
POINT DESCRIPTION
CCN
POINT NAME
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT ID
BACNET
OBJECT NAME
Run Status STATUS R N/A
0=Timeout,
1=Ready,
2=Recyle,
3=Startup,
4=Running,
5=Demand,
6=Ramping,
7=Autorest,
8=Override,
9=Tripout,
10=Control Test,
11=Lockout,
12=Pumpdown,
13=Prestart
AV:34 status_1
Service Ontime S_HRS R/W hr N/A 0 to 32767 AV:35 s_hrs_1
Shunt Trip Relay TRIPR OFF/ON BV:17 tripr_1
Stall Protection Counts SPC R N/A 0 to 5 AV:36 spc_1
Start Complete START_OK FALSE/TRUE BV:18 start_ok_1
Stop Fault AMPSTOP NORMAL/ALARM BV:10 ampstop_1
System Alert/Alarm SYS_ALM R N/A
1=Normal
2=Alert
3=Alarm
AV:37 sys_alm_1
System Cooling Demand Level R N/A N/A AV:9006 cool_demand_level_1
System Demand Limiting Active/Inactive BV:2 dem_lmt_act_1
Target VFD Speed VFD_TRG R % N/A 0 to 100 AV:38 vfd_trg_1
Torque Current TORQ_I R A N/A 0 to 99999 AV:39 torq_i_1
Tower Fan Relay High TFR_HIGH OFF/ON BV:19 tfr_2_1
Tower Fan Relay Low TFR_LOW OFF/ON BV:20 tfr_1_1
User Defined Analog 1 R N/A N/A AV:2901 user_analog_1_1
User Defined Analog 2 R N/A N/A AV:2902 user_analog_2_1
User Defined Analog 3 R N/A N/A AV:2903 user_analog_3_1
User Defined Analog 4 R N/A N/A AV:2904 user_analog_4_1
User Defined Analog 5 R N/A N/A AV:2905 user_analog_5_1
User Defined Binary 1 BV:2911 user_binary_1_1
User Defined Binary 2 BV:2912 user_binary_2_1
User Defined Binary 3 BV:2913 user_binary_3_1
User Defined Binary 4 BV:2914 user_binary_4_1
User Defined Binary 5 BV:2915 user_binary_5_1
Vaporizer Temp VAP_TEMP R °F N/A -40 to 245 AV:45 vap_temp_1
VFD Cold Plate Temp CP_TEMP R °F N/A 0 to 300 AV:46 cp_temp_1
VFD Start VFDSTART NO/YES BV:21 vfdstart_1
CHW Chilled Water
R—Read
VFD Variable Frequency Drive
W—Write