Specifications
107
Fig. 53 — 23XRV Controls Schematic
a23-1641
NOTES:
1. This feature is standard in the 23XRV controls, but requires
a controller with a non-grounded 4-20mA or 1-5Vdc output
signal, not by Carrier.
2. This feature is standard in the 23XRV controls, but requires
an external controller with a non-grounded 4-20mA output
signal, not by Carrier.
3. This feature is standard in the 23XRV controls, but requires
a sensor package option, by Carrier. (Item #3 see option
listing.)
4. Pins shown for reference only. Actual pin layout not shown.
5. This feature is standard in the 23XRV controls. Controllers
monitoring this signal must have a non-grounded input with
a maximum impedance of 500 ohms.