Product data
8
23XRV DIMENSIONS (NOZZLE-IN-HEAD WATERBOX)
23XRV DIMENSIONS (MARINE WATERBOX)
*Assumes both cooler and condenser nozzles on same end of chiller.
†1 or 3 pass length applies if cooler is a 1 or 3 pass design.
NOTES:
1. Allow at least 3 ft (915 mm) overhead clearance for service rigging
for the compressor.
3. Certified drawings available upon request.
4. Marine waterboxes may add 6 in. (152 mm), to the width of the
machine. See certified drawings for details.
5. ‘A’ length and ‘B’ width dimensions shown are for standard
150 psig (1034 kPa) design and flange connections. The
300 psig (2068 kPa) design will add length. See certified drawings.
6. Dished head waterbox covers not available for the 3-pass design.
HEAT EXCHANGER
SIZE
A (Length, with Nozzle-in-Head Waterbox)
B (Width) C (Height)
1 Pass 2-Pass* 3 Pass
30 to 32
35 to 37
40 to 42
45 to 47
50 to 52
55 to 57
HEAT EXCHANGER
SIZE
A (Length, Marine Waterbox)
B (Width)
C (Height)2-Pass* 1 or 3 Pass†
30 to 32
See unit
certified
drawings
35 to 37
40 to 42
45 to 47
50 to 52
55 to 57
B
(WIDEST POINT)
2’ MIN
(610 mm)
4’-10” MIN
(1475 mm)
A
C
FRAME R COMPRESSOR 3’-0” (915mm)
RECOMMENDED OVERHEAD SERVICE CLEARANCE
MOTOR SERVICE
CLEARANCE
1’-10” (559 mm)
TUBE REMOVAL
SPACE FOR
EITHER END
SIZES 30-32, 40-42
50-52
14’-3” (3848 mm)
SIZES 35-37, 45-47
55-57
14’-0” (4369 mm)
SERVICE AREA
4’ MIN
(1219 mm)
23XRV DIMENSIONS
a23-1646
Dimensions
2. Dimensions are approximate
mm
4369
4890
4521
5042
4547
5067
4181
4702
4359
4880
4388
4909
4369
4890
4439
4959
4451
4972
1930
1930
2045
2045
2127
2127
2200
2200
2299
2299
2305
2305
mm
4496
5017
4642
5163
4661
5182
mm
4997
5518
5086
5607
5093
5613
mm
2067
2067
2076
2076
2159
2159
mm
mm mm mm