TP ---PAC, TP ---PHP TP ---NAC, TP ---NHP Performance™ Series AC / HP Thermostat Installation Instructions A07049 Programmable Control A07048 Non-- Programmable Control Designed and Assembled in the U.S.A. NOTE: Read the entire instruction manual before starting the installation. US patents: US7287709 B2, US20080147242 A1, USD582800 SI, US20060165149 A1, US6956463 B2.
TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 INSTALLATION CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . 3 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 SYSTEM START--UP AND CHECKOUT . . . . . . . . . . . . . . . . . . . . . . 39 OPERATIONAL INFORMATION . . . . . . . . .
INTRODUCTION Carrier’s 7-- day, 5/2-- day, 1-- day programmable and non-- programmable Performance Series Thermostat Control is a wall-- mounted, low-- voltage temperature control in either a single unit or a two-- piece unit. In two-- piece configuration, the relays are located near the equipment and a two-- wire connection is used between the Display Module and the Equipment Control Module. Single-- piece installation requires more wiring and results in a higher profile.
INSTALLATION CONSIDERATIONS Power This control is powered by 24VAC only. It requires 24VAC (Rh and/or Rc and C terminals) of the low-- voltage transformer to be connected to it for proper operation. It will not operate without these 2 connections. Rh and Rc are connected via PCB breakout jumper. See Fig. 1. For applications using two 24VAC transformers, one in the indoor unit and one in the outdoor unit, connect the common from each to the C terminal. Connect R from the indoor unit to the Rh terminal.
A07052 Fig. 1 - PCB Breakout Jumper Models There are programmable and non-- programmable models for all applications. They can be configured for AC or HP installations, allowing it to be used in place of all Carrier thermostats. Programmable thermostats may be configured as non-- programmable if user desires. Outdoor Temperature Sensor The outdoor air temperature sensor is not included with the AC/HP Control. It is available as an accessory, part number TSTATCCSEN01-- B.
Remote Indoor Temperature Sensor A remote temperature sensor may be used with the programmable heat pump and programmable air conditioner thermostats where it is desirable to install the thermostat in a limited access location while measuring the temperature in the living space. The remote room sensor may be used as a stand alone or average with local sensor. Two--Piece Thermostat Configuration The Performance Series AC/HP Control can be installed in one of two configurations.
INSTALLATION ! CAUTION UNIT DAMAGE HAZARD Failure to follow the recommended wiring practices could result in damage to the wall control and personal property. Improper wiring or installation may damage AC/HP Control. Check to make sure wiring is correct before proceeding with installation or turning on power. Installation Notes: S No part of the control should be installed directly outdoors or in a cabinet outdoors. S Never remove the thermostat board from the plastic housing.
A13295 Fig. 2 - Coil Excess Wiring A07754 Fig.
Carton contains the following components. See Fig. 3 for programmable models or Fig. 4 for non-- programmable models. 1. Display Module 2. Stand-- off for Equipment Control Module 3. Screws and pig tail 4. Equipment Control Module A07755 Fig. 4 - TP-- NAC / TP-- NHP Carton Contents 1. 2. 3. 4. Display Module Stand-- off for Equipment Control Module Screws and pig tail Equipment Control Module AC/HP Control Location AC/HP Control should be mounted: S Approximately 5 ft (1.5m) from floor.
Close to or in a frequently used room, preferably on an inside partitioning wall. S On a section of wall without pipes or duct work. AC/HP Control should NOT be mounted: S Close to a window, on an outside wall, or next to a door leading to the outside. S Exposed to direct light or heat from a lamp, sun, fireplace, or other temperature-- radiating objects which could cause a false reading. S Close to or in direct airflow from supply registers and return-- air registers.
! CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation. Improper wiring or installation may damage AC/HP Control. Check to make sure wiring is correct before proceeding with installation or turning on power. 1. Turn off all power to equipment. 2. If an existing thermostat is being replaced a. Remove existing thermostat from wall. b. Disconnect wires from existing thermostat, 1 at a time. c.
Two--Piece Installation The following steps should be followed for the installation of the two-- piece configuration. NOTE: The 2-- wire pigtail is not intended to support the weight of the User Interface. Do not hang the User Interface from the equipment Control Module screw terminals. 1. Remove mounting plate from back of Display Module by pressing the two tabs on the bottom edge and pulling away. See Fig. 5 and 6. A07225 Fig.
A07226 Fig. 6 - Take Apart 2. Route wires through large hole in mounting base. Level mounting base against wall (for aesthetic value only—Display Module need not be leveled for proper operation) and mark wall through 4 mounting holes. To avoid unintended bending of wall plate plastic, use all 4 screws and anchors. See Fig. 7.
A07165 Fig. 7 - Backplate Mounting 3. Drill two 3/16-- in. mounting holes in wall where marked. Thermostat may be mounted to a standard junction box, if desired. Hole pattern on thermostat mounting base matches junction box mounting holes. 4. Secure rear plastic mounting base to wall with 4 screws and anchors provided. To avoid unintended bending of wall plate plastic, use all 4 screws and anchors. Make sure all wires extend through hole in mounting base. 5.
Control Module Wiring Guide Relays OAT RRS {SRTN HUM D1 dry contact D2 connect V+ to user interface Vg Rc Rh W / W1 G Y/Y2 C O/W2/B Y1 OAT / RRS return Y used for single stage cooling Y1 used for multi-speed cooling Y1 = stage 1 Y2 = stage 2 A07687 HUM terminal is not used on this model. Fig.
A07166 Fig. 9 - Secure Wires to Terminal Strip A07167 Fig.
NOTE: The 2-- wire pigtail is not intended to support the weight of the User Interface. Do not hang the User Interface from the equipment Control Module screw terminals. S Red is V+ S Black is Vg 7. Push any excess wire into wall and against mounting base. Seal hole in wall to prevent air leaks. Leaks can affect operation and cause incorrect temperature measurement. 8. Make sure to attach 2-- wire pigtail to Display Module mounting base. It is packed loose in the box from the factory.
10. Find suitable indoor mounting location for Equipment Control Module, either near or on equipment. See Fig. 12. IMPORTANT NOTE: Equipment Control Module should not be mounted to duct work or below any other controls or equipment (i.e. humidistat, humidifier, etc.) A07217 Fig. 12 - Equipment Control Module on Equipment 11. Route wires through rear of Equipment Control Module using either a clearance hole or supplied standoff. See Fig. 13.
A07227 Fig. 13 - Standoff NOTE: Standoffs are provided as an aid when installing Equipment Control Module on inside equipment or a solid wall. 12. Match and connect equipment wires to proper terminals of each connector block being careful not to over tighten the screws. Correct polarity must be observed when connecting the two wires from the Equipment Control Module to the thermostat mounting base. If wires are connected incorrectly, the Display Module will not operate. See Fig. 8, 8 and 9. 13.
A07218 Fig. 14 - Cover on Equipment Control Module 14. Turn on power to equipment. On power up, all display segments will light for 5 sec. For the next 5 sec a 2-- digit code appears on large display which identifies AC/HP Control configuration. Refer to Option 33. a. AC — 1-- stage air conditioner, AC, with furnace or fan coil b. HP — 1-- stage heat pump, HP only with fan coil c. H — heating only system, furnace only or fan coil with electric heat only d. C — cooling only system, AC with fan coil e.
Single--Piece Installation The following steps should be followed for the installation of the single-- piece configuration. 1. Remove cover from Equipment Control Module by pressing the two tabs on the bottom edge and pulling away. Route wires through large hole in Equipment Control Module. Level Equipment Control Module against wall (for aesthetic value only - Equipment Control Module need not be leveled for proper operation) and mark wall through 4 mounting holes.
A07219 Fig. 15 - Equipment Control Module 5. Match and connect equipment wires to proper terminals of each connector block. 6. Push any excess wire into wall and against Equipment Control Module. Seal hole in wall to prevent air leaks. Leaks can affect operation and cause incorrect temperature measurement. 7. Remove 2-- wire pigtail from thermostat mounting base and attach to Equipment Control Module terminal block (terminals V+ and Vg).
A07220 Fig. 16 - Reattach Display Module 9. Turn on power to equipment. On power up, all display segments will light for 5 sec. For the next 5 sec a 2-- digit code appears on large display which identifies AC/HP Control configuration. Refer to Option 33. a. AC — 1-- stage air conditioner, AC, with furnace or fan coil b. HP — 1-- stage heat pump, HP only with fan coil c. H — heating only system, furnace only or fan coil with electric heat only d. C — cooling only system, AC with fan coil e.
be properly set by the installer. (Only those marked with an asterisk * below are available to the homeowner.) The homeowner configurations are described in the owner’s manual. A special procedure allows entry into the configuration mode. Description of each selection and how to use the configuration mode follows.
Option 20 — Outdoor Air Temperature Offset Adjustment Option 21* — Keypad Lockout Option 24* — Programmable/Non-- Programmable (programmable models only) Option 25* — Number of Programmable Periods per Day (programmable models only) Option 26 — Minimum Cooling Setpoint Option 27 — Maximum heating Setpoint Option 28 — UV Light Reminder Option 30* — Programmable Fan (programmable models only) Option 31* — Daylight Savings Time Configuration (programmable models only) Option 32 — Furnace Heat Staging Option 33
WHILE IN CONFIGURATION MODE The option number is displayed in the heat setpoint location and the configuration setting is displayed in the cool setpoint location. On the TP-- PAC/PHP (programmable) models, a box will surround the option number. The mode button is used to move the box between the two displayed values. The soft keys below the listed values may also be used to move the box between selected values. The value inside the box is changed by using the UP/DOWN buttons.
Defaults HP model defaults to HP. AC model defaults to AC. Option 02 — Clean Filter Timer Select hours of blower operation (heating, cooling, or fan) before CHECK FILTER icon is displayed. With OF selected, icon will never come on, disabling this feature. Time selection can range from 800 to 7200 hr by selecting numbers 1 through 9. (Time is 800 X number selected.) Default is 4 (3200 hr).
RRS SRTN Sensor 1 Sensor 2 Sensor 3 Sensor 4 A09130 Fig. 17 - Remote Room Sensor - Parallel Wiring This selection determines which sensor the control will use for measuring room air temperature. Room air temperature can be sensed in one of three ways; the local sensor (L) located on the Display Module, the remote room air sensor (r), or the average of local and remote sensors (Lr). Settings are L, r, Lr. Default is L.
Option 07 — Zoning This selection should be set to On when the thermostat is to be used as part of a zoning system. It is assumed that the zoning equipment will take care of time guard and cycle timers. The minimum on time is still controlled by the thermostat. Default is OF (off). Option 08 — Auxiliary Heat Lockout Temperature This selection is available on heat pump systems with a valid outdoor temperature sensor connected. Available settings are: Off, 5, 10, 15, 20, 25, 30, 35, 40, 45, 50, 55.
Option 11 — Deadband Setting Between Heat & Cool This option is not available on Heat Only and Cool Only systems. This selection is to allow the installer to choose how much differential exists between the heating and cooling setpoints. Allowable selections are 1-- 6. Default is 2. Option 12 — Smart Recovery Smart Recovery OF (off) means setpoints change precisely at setback recovery time. Thirty, 60, or 90 selects the number of minutes recovery starts before programmed recovery time.
Option 16 — Maximum Cycles Per Hour This selection limits the number of cycles per hour that the thermostat allows the system to operate. Selections are 2, 4, 6. 2 — The heating and cooling outputs will be energized no more than 2 times per hour. When an output is energized, it will not be energized again for 30 minutes. 4 — The heating and cooling outputs will be energized no more than 4 times per hour. When an output is energized, it will not be energized again for 15 minutes.
Option 19 — Dry Contact Configuration (programmable models only) There are 2 available selections, OF and 1. OF — The dry contact is always de-- energized. 1 — The dry contact will be energized for the specified number of minutes per hour. This selection is programmable by period. When this selection is changed from OF to 1, the period icons are shown and the minute segments of the clock display are shown.
When the keypad lock selection is turned on, the padlock icon will be displayed. To unlock the keypad, press and hold the UP/DOWN buttons simultaneously for five seconds. When the keypad is unlocked, the padlock icon will turn off. The keypad will remain unlocked for two minutes after the last button press. After two minutes with no button presses, the keypad will lock again. The keypad will not lock in the software configuration mode or in the installer test mode. Default is OF (off).
Option 22 — High Cool Latch Temperature (only available if outdoor sensor is present) An outdoor sensor is required for high cool latch feature. This selection is only available when Option 1 is set to H2, A2, or h2 and when Option 7 (zoning) is set to OF (off). Configuration settings are OF (off), 80, 85, 90, 95, 100, 105, 110, On. OF (off) — Cooling always starts in low stage (Y1) and stages up to high stage (Y1 and Y/Y2) when demand is sufficient and staging timer constraints have been satisfied.
On — The Y1 and Y/Y2 outputs are simultaneously energized to satisfy all heating demands. Default is OF (off). Option 24 — Programmable/Non-- Programmable This selection allows the installer to configure the thermostat as either programmable or non-- programmable. Selections are P, nP. Default is P (programmable models only). Option 25 — Number of Programmable Periods This selection allows the installer to configure the thermostat for two or four periods per day.
Option 27 — Maximum Heating Setpoint This selection allows the installer to configure the maximum heating setpoint. The range is based on the adjustable deadband value Option 11, such that the minimum of the range is 50_F/10_C and the maximum is 90_F/32_C minus the deadband. Default is 88_F/31_C (based on the adjustable deadband default = 2).
Option 31 — Daylight Savings Time Configuration (programmable models only) This selection allows the installer to set the thermostat to automatically change by one hour on the specified day, month, and week specified. OF (off) — Daylight Savings Time Function disabled. 1,2 On — The first time the UP/DOWN button is pressed, the value of this selection changes from OF (off) to 1. When 1 is displayed, the days of the week and clock digits will be turned on.
Option 33 — Single or Two-- Piece Installation This configuration allows the thermostat to compensate for the amount of heat generated by the thermostat electronics to allow more accurate sensing of the temperature sensor. The amount of heat compensation will be different between single installation and two-- piece installation. Range: 1P or 2P 1P — The installation is single piece. 2P — The installation is two separate pieces. Default is 2P.
If the outdoor air temperature is below 12_F/-- 11_C and there is sufficient demand for the equipment to be on, then the fan output is turned back on and the W/W1 output is energized. In a two speed unit the Y/Y2 output should be energized in addition to the W/W1 output. NOTE: All temperature boundaries have a +/-- 2_ hysteresis. Factory default is OF (Off). Option 99 — Reset to Factory Defaults Use this capability to reset the stat to “out of the box” conditions.
SYSTEM START--UP AND CHECKOUT The AC/HP Control is designed with a built-- in installer test capability. It allows easy operation of equipment without delays or setpoint adjustments to force heating or cooling. To enable installer test mode, press and hold the fan button for 15 seconds. After 10 seconds, the thermostat will enter Configuration Mode. Continuing to hold the Fan button through 15 seconds will cause the thermostat to enter Installer Test Mode.
TO TEST FAN Fan button switches FAN icon between AUTO and On. While On is displayed, G output will be energized, turning fan on. On some fan coils, fan continues to operate for 90 sec after G signal is removed. Final Settings Be sure to press DONE to exit installer setup mode. If the system is to be left in operation after installation is complete, use MODE button to select between HEAT, COOL, or AUTO to provide desired operation of heating, cooling, or auto.
The FAN button may be used to select between AUTO (fan on only with equipment) and On (fan on continuously) fan modes. For further information on temperature selection and programming, refer to Homeowner’s Guide. Setting The Clock, Calendar, Daily Schedule, and Vacation Settings (programmable models only) To set the clock, press the SET button once. The Clock will be displayed at the bottom center of the screen.
Vacation Setpoints A special set of temperature setpoints exist which are active in vacation mode. They are adjustable by the homeowner, are exclusively for vacation mode, and are remembered from one vacation selection to the next. See Table 2 for default values.
Ten-- Minute Staging Timer In multistage heating or cooling, this timer prevents any higher stage from turning on until preceding stage has been on for 10 minutes. When staging between compressor and electric heat or between compressor and furnace heat, the time is configurable. The timer is configurable via Option 17. This timer is overridden if temperature error is greater than 5_ (usually due to a large change in desired temperature) and equipment stages up in 60 second intervals.
Three-- Minute Minimum on Time In normal operation, when a stage turns on, it will not turn off for a minimum of 3 minutes. If the setpoint is changed, this timer is canceled, allowing the equipment to turn off immediately when the demand is removed. Heat/Cool Setpoints (Desired Temperature) A minimum difference of 1_ and maximum of 6_ is enforced between heating and cooling desired temperatures. This is done by allowing 1 setting to “push” the other, to maintain this difference.
Programmable Fan (programmable models only) The fan output can be programmed based on period of the day. When programming for each day and period the fan can be set to On or AUTO. If the fan button is pressed to change from On to Auto or vice versa when programmable fan has been enabled, the manual change will only remain in effect until the next program period, when the programmable fan setting will be changed per the scheduled setting.
Temperature Offset After Power Cycle To compensate for internal heat build-- up from the electronics in the thermostat, the thermostat will add an offset to the actual temperature that it measures. If the thermostat power is cycled quickly, one can witness an immediate increase in the actual temperature displayed due to this added offset. The thermostat display will return to the actual room temperature after several minutes of operation.
E3 - If AC/HP Control cannot properly read outdoor temperature, and it is needed for proper operation, display will indicate “-- - ” in the outdoor temperature location. E4 - If AC/HP Control’s internal memory fails, E4 will be displayed. Replace AC/HP Control. Table 3 can be used as a troubleshooting tool for determining which outputs will be active for a particular configuration and each operating mode.
Table 3 – Equipment Configuration Outputs For COOL, HEAT and Emergency Heat modes, the following chart shows the state for each output in each stage of operation Equip Config SS AC Opt 1 = AC Tstat Model TP--- PAC TP--- NAC COOL STG 1 COOL STG 2 HEAT STG 1 HEAT STG 2 HEAT STG 3 HEAT STG 4 EM HEAT STG 1 EM HEAT STG 2 Y/Y2 --- --- W/W1 --- --- --- --- --- --- --- --- --- --- W/W1 O/W2/B (if Opt.
Table 3 - Equipment Configuration Outputs (cont.) Equip Config Tstat Model COOL STG 1 COOL STG 2 2SPD HP Opt 1 = H2 VS = B Opt 10 = H TP--- PHP TP--- NHP Y1/W2 Y1/W2 Y/Y2 Heat Only Unit Opt 1 = H TP--- PHP TP--- NHP TP--- PAC TP--- NAC Cool Only Unit Opt 1 = C TP--- PHP TP--- NHP TP--- PAC TP--- NAC --- --- Y1/W2 HEAT STG 1 HEAT STG 2 Y1/W2 O/W2/B Y1/W2 Y/Y2 O/W2/B --- --- W/W1 If HP or RH board & Opt.
WIRING DIAGRAMS Display module Display module wall mount Equipment Control Module V+ Fan Coil Heat Pump V+ O O V+ Vg V+ RVS/Heat Stage 2 Vg O/B W2 W3 W2 Vg Vg Heat Stage 1 W/W1 W2 Compressor Y/Y2 Y Not Used Y1 Y Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C COM COM Outdoor Air Temp OAT Remote Room Sensor RRS Outdoor Sensor * OAT/RRS Com OAT/RRS Remote Room Sensor * * Indicates connection may not be req
WIRING DIAGRAMS(cont.) Thermostat Fan Coil O RVS/Heat Stage 2 O/B W2 W3 Heat Stage 1 W/W1 W2 Compressor Y/Y2 Y Not Used Y1 Heat Pump O W2** Y Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C COM COM Outdoor Air Temp OAT Remote Room Sensor RRS Outdoor Sensor * OAT/RRS Com OAT/RRS Remote Room Sensor * * Indicates connection may not be required/available. ** Some heat pumps may designate W1. A09154 Fig.
WIRING DIAGRAMS(cont.) Thermostat Fan Coil O RVS/Heat Stage 2 O/B W2 W3 Heat Stage 1 W/W1 W2 Compressor Y/Y2 Not Used Y1 Fan G G 24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C Aux. Connection COM Outdoor Air Temp OAT Remote Room Sensor RRS Outdoor Sensor * OAT/RRS Com OAT/RRS Remote Room Sensor * * Indicates connection may not be required/available. A09155 Fig.
WIRING DIAGRAMS(cont.) Thermostat Fan Coil Air Conditioner O RVS/Heat Stage 2 O/B W2 W3 Heat Stage 1 W/W1 W2 Compressor Y/Y2 Y Not Used Y1 Y Fan G G 24VAC Hot Heating Rh R R COM COM 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C Outdoor Air Temp OAT Remote Room Sensor RRS Outdoor Sensor * OAT/RRS Com OAT/RRS Remote Room Sensor * * Indicates connection may not be required/available. A09175 Fig.
WIRING DIAGRAMS(cont.) Thermostat Fan Coil O RVS/Heat Stage 2 O/B W2 W3 Heat Stage 1 W/W1 W2 Compressor Y/Y2 Not Used Y1 Fan G G 24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C Aux. Connection COM Outdoor Air Temp OAT Remote Room Sensor RRS Outdoor Sensor * OAT/RRS Com OAT/RRS Remote Room Sensor * * Indicates connection may not be required/available. A09156 Fig.
WIRING DIAGRAMS(cont.) Thermostat Furnace * Heat Stage 2 O/B W2 W2* Heat Stage 1 W/W1 W/W1 Compressor Y/Y2 Y/Y2 Not Used Y1 Air Conditioner Y Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C COM COM Outdoor Air Temp OAT Remote Room Sensor RRS Outdoor Sensor * OAT/RRS Com OAT/RRS Remote Room Sensor * * Indicates connection may not be required/available. A09157 Fig.
WIRING DIAGRAMS(cont.) Thermostat RVS/Heat Stage 2 O/B W2 Heat Stage 1 W/W1 Compressor Y/Y2 Not Used Y1 Fan G G 24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C Outdoor Air Temp OAT Remote Room Sensor RRS OAT/RRS Com OAT/RRS C A09158 Fig.
WIRING DIAGRAMS(cont.) Thermostat Furnace Air Conditioner W2 RVS/Heat Stage 2 O/B W2 Heat Stage 1 W/W1 W/W1 Compressor Y/Y2 Y/Y2 Not Used Y1 Y Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C COM COM Outdoor Air Temp OAT Remote Room Sensor RRS Outdoor Sensor * OAT/RRS Com OAT/RRS Remote Room Sensor * * Indicates connection may not be required/available. A09159 Fig.
WIRING DIAGRAMS(cont.) Single-Stage Furnace Thermostat RVS/Heat Stage 2 O/B W2 Heat Stage 1 W/W1 Compressor Low Y1 Compressor High Y/Y2 Y/Y2 Fan G G 24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C Single-Stage Air Conditioner W/W1 Y R* COM Outdoor Air Temp OAT Remote Room Sensor RRS Outdoor Sensor * OAT/RRS Com OAT/RRS Remote Room Sensor * COM * Indicates connection may not be required/available.
THERMOSTAT CONFIGURATION RECORD Installer _________________________ Model Number _____________________________ Date _______________________ A. Hardware Configuration __________ Seal Hole In Wall B. Mode Settings __________ Mode (Off, Heat, Cool, Auto, Em Heat) __________ Heating Setpoint Value __________ Cooling Setpoint Value __________ Fan (Auto or On) C. Home, Away, Sleep Settings Home Away Sleep Heat Cool ____ ____ ____ ____ ____ ____ D.
E Configuration Options Option 01 Option 02 Option 03* Option 04 Option 05 Option 06 Option 07 Option 08 Option 10 Option 11 Option 12 Option 13 Option 15 Option 16 Option 17 Option 18* Option 19 Option 20 _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ Equipment Type Clean Filter Timer Adjustment Fahrenheit/Centigrade Selection Fan (G) on with W/W1 Selection Room Air Temperature Sensing Cooling Lockout Below 55_F/13_C Selection (only available i
E Configuration Options (cont) Option 21* Option 22 Option 23 Option 24* Option 25* Option 26 Option 27 Option 28 Option 30* Option 31* Option 32 Option 33 Option 41 Option 44 Option 99 _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ _____ Keypad Lockout High Cool Latch Temperature High Heat Latch Temperature Programmable/Non-- Programmable (programmable models only) Number of Programmable Periods Per Day (programmable models only) Minimum Cooling Setpoint Maximum Heati
NOTES 62
NOTES 63
NOTES 64
997--- 060370--- 7--- R Copyright 2013 Carrier Corporation 7310 W Morris St. Indianapolis, IN 46231 TP---PAC ---07SI Replaces: TP--- PAC--- 06SI Edition Date: 07/13 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.