Service manual

4-10T-294-01
Table 4-1. Electrical Control Positions -- BELOW --10
_
__
_
C(+14
_
__
_
F), or --5
_
__
_
C(+23
_
__
_
F) optionally
CONTROL CIRCUIT COOLING Holding Zone
**Dehumidifica-
tion
HEATING DEFROST
Compressor Contactor
(CH)
Energized De-energized ** ** De-energized
1
Condenser Fan
Contactor (CF)
Energized De-energized ** ** De-energized
High Speed Evaporator
Contactor (EF)
De-energized De-energized
Refer to section
3.1.7.a.2
Refer to section
3.1.7.a.2
De-energized
2
Low Speed Evaporator
Contactor (ES)
Energized Energized
Refer to section
3.1.7.a.2
Refer to section
3.1.7.a.2
De-energized
Heater Contactor (HR)
De-energized De-energized ** ** Energized
INDICATING LIGHTS
Cool
ON OFF ** ** OFF
Defrost
OFF OFF ** ** ON
In-Range On -- If In-Range (Refer to paragraph 3.1.4, Code 30)
Heat
OFF OFF ** ** ON
POWER CIRCUIT
Compressor
Energized De-energized ** ** De-energized
Condenser Fan Motor
Energized De-energized ** ** De-energized
Heaters
De-energized De-energized ** ** Energized
Evaporator Fan Motors
Energized Energized ** ** De-energized
** Dehumi dification a nd heating modes do not operate at set points below --10
_
C (14
_
F), or --5
_
C (23
_
F) optionally
1
-- May be e nergized in defrost if snap freeze portion of defrost is run.
2
-- May be energized i n defrost if probe check portion of defrost is run.