Product data

Operation
The Stuck Gas Valve sequence is used to allow the system
to properly react to a failure mode of the HVAC unit when
the gas valve becomes stuck in the open position. When
this condition exists, the unit is unable to shut off the heat.
To minimizethis problem, theinternal limitswitch tripscaus-
ing the indoor fan to turn on and remain on until the gas is
manually shut off and the heat exchanger cools to normal
temperatures.
Without this feature, a VVTt system operating normally
would close each of its zone dampers as space conditions
warmed to set point. This causes the heated air to be re-
circulatedback throughtheunit, further aggravatingthe over-
heating problem. With the Stuck Gas Valve sequence, the
VVT dampers open to their configured maximum damper
position. This allows space temperatures in the building to
rise to higher than normal temperature levels. However,
this sequence reduces the temperature build-up in the unit
and keeps the heat exchanger operating within tempera-
tures to prevent failure.
During no system mode If the duct temperature rises to
greater than 175 F, the indoor fan is started. The fan will
remain on if that temperature does not drop below 150 F
after 3 minutes. The bypass damper will be closed, and all
zone dampers will opento theirmaximum position.A Stuck
Gas Valve alarm (SE-13) will be initiated.
During a cooling mode If the duct temperature does not
drop below 100 F within 10 minutes, the cooling mode will
be dropped for 10 minutes. The ‘‘No System Mode’’ logic
will test for this condition.
During a heating mode No action is required in this
mode.
Typical VVT system installation
19397