Specifications

Storage Failure (SF) Errors A Storage Failure
error is an error that corresponds to invalid information.
When an SF Error occurs, the monitor thermostat
replaces the invalid data in memory with factory selected
default values and the invalid information is not used to
determine system mode.
To clear an SF Error, enter the correct data at the monitor
thermostat by reconfiguring the associated options. See
Table 4 for a description of Storage Failure Errors.
Table 4 Storage Failure (SF) Errors
SF
ERROR
INFORMATION
AFFECTED
DEFAULT
VALUE(S)
SF01 Occupied Cooling Set Point 72
SF02 Occupied Heating Set Point 68
SF03 Cooling Set Point Low Limit 68
SF04 Heating Set Point High Limit 73
SF05
Unoccupied Cooling
Set Point
80
SF06
Unoccupied Heating
Set Point
65
SF07 Rotating Display OFF
SF08
Fahrenheit Temperature
Display
ON
SF09 Occupancy Period 1
MTWTF
6:00AM-
6:00PM
SF10 Occupancy Period 2
SF11 Occupancy Period 3
SF12 Occupancy Period 4
SF13 Occupancy Period 5
SF14 Occupancy Period 6
SF15 Occupancy Period 7
SF16 Occupancy Period 8
SF17 Schedule Number 0
SF18 Override Time Limit 1
SF19 Maximum Damper Position 15
SF20 Minimum Damper Position 0
SF23 ZD/RD Actuator ON
SF24 Counterclockwise Open ON
SF28 Fan Operation For Heat ON
SF30 Time Guard Between Modes OFF
SF32 LAT Monitoring ON
SF33
First Stage Cooling
Temperature Limit
45
SF34
Second Stage Cooling
Temperature Limit
50
SF35
First Stage Heating
Temperature Limit
110
SF36
Second Stage Heating
Temperature Limit
105
SF37 Auxiliary Relay 1
SF38 Optimize Staging ON
SF39 Temperature Lockouts OFF
SF40 Heating Lockout Set Point 60
SF41 Cooling Lockout Set Point 40
SF42 System Mode Demand 1
SF43 System Mode Re-Select 30
SF44 Minimum Heat Run Time 0
SF45 Pre-Occupancy Purge OFF
SF46
Zone Temperature Sensor
Calibration
Factory
Calibrated
SF47
Remote Room Sensor
Calibration
Factory
Calibrated
SF
ERROR
INFORMATION
AFFECTED
DEFAULT
VALUE(S)
SF48
Duct Temperature Sensor
Calibration
Factory
Calibrated
SF50 Fan Status Switch OFF
SF51 Room Sensor 1
SF53
DX Coil Temperature
Sensor
OFF
SF54
DX Coil Temperature
Sensor Calibration
Factory
Calibrated
SF55
Outdoor Air Temperature
Sensor
OFF
SF56
Outdoor Air Temperature
Sensor Calibration
Factory
Calibrated
SF57
Supplemental Heat
Lockout
OFF
SF58
Supplemental Heat
Callers
OFF
SF61 Alarm System Name
Network
Configured
(CCN
Alarms)
SF65 Error Code Display OFF
SF67 Alternate Information OFF
SF68 Comfort Trend Demand 0
SF69 Comfort Trend Time Limit 0
SF70 HVAC Usage Meter Data OFF
SF71 Override Usage Meter Data OFF
SF73 Heat Mode Error Set Point 0
SF74 Cool Mode Error Set Point 140
SF75 Device Element Address 0
SF76 Security Level 1
SF77 Device Bus Number 0
SF78 Scanning Control 1
SF79 Network Time Broadcast OFF
SF80 Network Time Request OFF
SF81 Receive Network Time OFF
SF82 Broadcast Acknowledger OFF
SF83 Global Schedule Broadcast OFF
SF85 Holiday Schedules 0
SF86 Equipment Priority 7
SF87
Communication Failure
Retry Time
10
SF88 Re-Alarm Time 30
SF89 IAQ System ON
SF90 Optimal Start Time Limit 4
SF92
Demand Limit Group
Number
0
SF93 Local IAQ Sensor OFF
SF94 IAQ Economizer Delay 10
SF95
IAQ Maximum Space
Temperature Reset
OFF
SF96
Humidity Sensor/Filter
Switch
0
SF97
Humidity Sensor
Calibration
Factory
Calibrated
SF98 Alarm Routing Control
Network
Configured
(11000000)
SF100 HVAC Meter Enable ON
SF101 Override Meter Enable ON
SF102
HVAC Override Meter
Enable
ON
SF104
HVAC Override Meter
Data
OFF
SF106 System Fan Control OFF
SF107 System Cool Control OFF
SF108 System Heat Control OFF
35