Specifications
When zone temperature conditions exceed the desired oc-
cupied level, if first stage heating or cooling is able to im-
prove the occupied level, second stage heating or cooling is
not required.
The monitor thermostat uses Optimized Staging to follow
zone conditions and determine when use of first stage is im-
proving zone conditions. If zone conditions are not improv-
ing, or are becoming worse, the monitor thermostat will en-
ergize the second stage of heating or cooling.
System Status Display — The monitor thermostat in-
dicates the system mode and equipment operation by dis-
playing system annunciators. FAN is displayed when the
monitor thermostat energizes the fan relay. COOL is dis-
played when the monitor thermostat energizes a cooling re-
lay. HEAT is displayed when the monitor thermostat ener-
gizes a heating relay. When a second stage of heating or cooling
is energized, a decimal point is displayed between the set
points.
System Mode Reselect — The System Mode Rese-
lect function is the amount of time the monitor thermostat
will wait between checking for a change in system mode.
The System Mode Reselect option is configured through cat-
egory 4, option 16. The range of values is 0 to 480 minutes
in 1 minute increments. The default is 30 minutes.
System Mode Reselect is activated when the following
requirements are met:
• the monitor thermostat is configured as a VVTt Monitor
or Monitor Only thermostat
• the monitor thermostat is in system heating or cooling mode
• there are simultaneous zone callers for both heating and
cooling.
If there are simultaneous heating and cooling callers for
the entire length of the System Mode Reselect and there are
more callers for the opposite mode with greater demand, the
monitor thermostat uses the system mode function to select
a new system mode. If the monitor thermostat chooses the
system mode opposite from the currently selected system mode,
it releases the current system mode and initiates the new sys-
tem mode. If the monitor thermostat chooses the same sys-
tem mode as currently selected, it continues in that system
mode. If the monitor thermostat cannot select a system mode
because system mode demand cannot be attained, it releases
the current system mode.
To disable the System Mode Reselect option, configure
the value to zero.
System Time Guards — The monitor thermostat has
different system time limits (time guards) which prevent an
individual system heating or cooling mode from being se-
lected after the system mode has been released or after the
monitor thermostat receives power.
HIGH/LOW TEMPERATURE LIMITTIME GUARD — This
feature functions to keep the HVAC equipment operating to
reduce equipment cycling. By monitoring the supply-air tem-
peratures, the monitor thermostat can adjust operation to pre-
vent tripping of the heating/cooling temperature limits.
When the supply-air temperature exceeds the first or sec-
ond stage Heating or Cooling Temperature Limit the corre-
sponding stage of heating or cooling is disabled.
If the monitor thermostat is in a system mode, it will re-
energize the appropriate stages of heating or cooling when
10 minutes have passed and the supply-air temperature is no
longer exceeding the first or second stage Heating or Cool-
ing Temperature Limit.
During equipment operation, when a limit is exceeded,
the following relays are deenergized:
• Second Stage Limit. The second stage relay (H2 or C2) is
deenergized.
• First Stage Limit. The first stage relay (H1 or C1) is
deenergized.
NOTE: When both first and second stage Heating or Cool-
ing Temperature Limits are exceeded during a system mode,
if the reference zone is no longer a zone caller and there are
zone callers for the opposite system mode, the monitor ther-
mostat ends the current system mode.
Construction System thermostats do not perform LAT (Leav-
ingAir Temperature) checking. Monitor-Only and VVT Moni-
tor thermostats receive supply-air temperature information
from the monitor thermostat, the bypass controller, each zone
controller zone damper supply air temperature sensor asso-
ciated with the system, and from the DX Coil Temperature
Sensor.
The highest and lowest supply-air temperatures are then
used to determine when a Heating or Cooling Temperature
Limit is exceeded.
When the LAT Monitoring option is set to ON, the moni-
tor thermostat maintains system heating and cooling supply
air temperature limits and enables the LAT algorithm.
When the LAT Monitoring option is set to OFF, the moni-
tor thermostat will not maintain heating and cooling supply
air temperature limits and the LAT algorithm is disabled.
To configure the LAT Monitoring option, set category 4,
option 4. Use the left set point buttons to toggle the option
ON and OFF. The default is ON.
First Stage Cooling Temperature Limit — If the entering air
temperature drops below the First Stage Cooling Tempera-
ture Limit and the LAT Monitoring function is ON, the moni-
tor thermostat will deenergize first stage cooling.
To configure the First Stage Cooling Temperature Limit
option, set category 4, option 5. Use the left set point but-
tons to raise or lower the set point until the desired tempera-
ture is shown. The range of acceptable values is 40 to 45 F,
in one-degree increments. The default is 45 F.
NOTE: The first stage limit cannot be set higher than the
second stage limit.
Second Stage Cooling Temperature Limit — If the entering
air temperature drops below the Second Stage Cooling Tem-
perature Limit and the LAT Monitoring function is ON, the
monitor thermostat will deenergize second stage cooling.
To configure the Second Stage Cooling Temperature Limit
option, set category 4, option 6. Use the left set point but-
tons to raise or lower the set point until the desired tempera-
ture is shown. The range of acceptable values is 45 to 50 F,
in one-degree increments. The default is 50 F.
First Stage Heating Temperature Limit — If the duct tem-
perature entering-air temperature rises above the First Stage
Heating Temperature Limit and the LAT Monitoring func-
tion is ON, the monitor thermostat will deenergize first stage
heating.
To configure the First Stage Heating Temperature Limit
option, set category 4, option 7. Use the left set point
buttons to raise or lower the set point until the desired tem-
perature is shown. The range of acceptable values is 110 to
180 F, in one-degree increments. The default is 110 F.
Second Stage Heating Temperature Limit — If the duct tem-
perature entering-air temperature rises above the Second Stage
Heating Temperature Limit and the LAT Monitoring func-
tion is ON, the monitor thermostat will deenergize second
stage heating.
To configure the Second Stage Heating Temperature Limit
option, set category 4, option 8. Use the left set point
buttons to raise or lower the set point until the desired tem-
perature is shown. The range of acceptable values is 105 to
160 F, in one-degree increments. The default is 105 F.
28