Specifications

LOCAL ZONE IAQ PROBLEM When the monitor ther-
mostat scans the bus to gather information to operate the sys-
tem it also gathers the IAQ status of the associated zone
controller and bypass. When a zone controller gives the moni-
tor thermostat the Zone In IAQ flag, the monitor turns on the
fan. If the IAQ Economizer Delay times out and one of its
zones still has an IAQ problem the monitor will qualify hu-
midity and outside air temperature against its lockout set points
and energize it economizer relay as long as humidity and
outdoor air are acceptable. When the Zone In IAQ either sat-
isfies or reaches its reset temperature it will not send the moni-
tor thermostat the Zone In IAQ flag and the monitor ther-
mostat will deenergize the economizer relay. It will also
deenergize the fan if the fan switch is in AUTO and there is
no mode or all of its zones are in the Unoccupied mode and
there is no mode.
SYSTEM IAQ PROBLEM When the monitor thermostat
gets a system IAQ flag from the bypass or its local IAQ sen-
sor alarms in the Monitor-Only operation, it starts the Sys-
tem IAQ mode. First the monitor gives all of the zone con-
trollers the system IAQ flag. The zone controllers then look
at their system IAQ option to determine if they are going to
participate in the system IAQ mode, if not, they will not send
the monitor the Zone In IAQ flag. If the System IAQ option
is on in each zone controller then the zone controllers will
look at their Reset Temperature window to determine if they
can do System IAQ. If the zone controllers are within their
reset window they will give the monitor the Zone In IAQ
flag and position their dampers at the maximum damper po-
sition. If the IAQ economizer delay times out and one of its
zones still has the Zone In IAQ flag active the monitor will
qualify humidity and outside air temperature against its lock-
out set points and energize its economizer relay as long as
humidity and outside air are acceptable. When the last Zone
In IAQ reaches its reset temperature or the system IAQ sen-
sor satisfies, the monitor will deenergize the economizer re-
lay. It will also deenergize the fan if the fan switch is in AUTO
and there is no mode or all of its zones are in the unoccupied
mode and there is no mode. The damper modulation for the
monitor’s zone is identical to the zone controller’s. When
the monitor has a System IAQ trip it will look at the system
mode and if the mode matches zone demand its zone will
participate in the System IAQ mode. If the system mode does
not match zone demand, it will use the Reset window. If the
Reset window check fails the monitor will look at duct tem-
perature and if the duct temperature will improve its space
conditions it will participate in the System IAQ mode.
IAQ ECONOMIZER DELAY The IAQ Economizer
Delay option controls how long the indoor fan will run
before the economizer is energized. With a Carrier integrated
economizer, the outside-air damper will go to the minimum
damper position whenever the fan is energized. If the moni-
tor thermostat is still receiving a Zone In IAQ flag after the
IAQ economizer delay has been timed out, the monitor ther-
mostat will energize the auxiliary (AUX) relay (economizer
relay). To configure the IAQ Economizer Delay option, set
category 14, option 3. The number of minutes will be shown.
The range of acceptable values is 5 to 30 minutes in 1 minute
increments. Use the left set point buttons to set the time limit
to the desired value. The default value is 10 minutes.
IAQ MAXIMUM SPACE TEMPERATURE RESET When
the IAQ mode brings in fresh outdoor air, the space tem-
perature will rise or fall depending on the outside air tem-
perature. The IAQ Maximum Zone Temperature Reset is the
maximum amount of deviance from the set point that a zone
will allow to satisfy IAQ requirements. The IAQ Maximum
Space Temperature option will keep the HVAC equipment
from entering heating or cooling unless the temperature change
is greater than the set point. The option is configured in
category 14, option 4. The set point can be configured from
0 to 10° F. The default value is F.
IAQ HUMIDITY LOCKOUT SET POINT When the IAQ
mode brings in fresh outdoor air, the space humidity will
rise or fall depending on the outside air humidity. The IAQ
Humidity Lockout Set Point is the maximum outdoor air rela-
tive humidity reading at which a zone will allow air to be
brought into the zone to satisfy IAQ requirements. The IAQ
Humidity Lockout Set Point option will keep the IAQ mode
from beginning unless the outdoor humidity is below ac-
ceptable levels. The option is configured in category 14, op-
tion 5. The set point can be configured from 0 to 100. The
default value is 0. The system relative humidity must be broad-
cast by a device (comfort controller) on the network.
IAQ LOW TEMPERATURE LOCKOUT When the IAQ
mode brings in fresh outdoor air, the space temperature will
rise or fall depending on the outside air temperature. The
IAQ Low Temperature Lockout Set Point is the minimum
outdoor air temperature reading at which zone will allow air
to be brought into the zone to satisfy IAQ requirements. The
IAQ Low Temperature Lockout Set Point option will keep
the IAQ mode from beginning unless the outdoor tempera-
ture is above the set point. The option is configured in
category 14, option 6. The set point can be configured from
0 to 110 F. The default value is 45 F.
IAQ HIGH TEMPERATURE LOCKOUT When the IAQ
mode brings in fresh outdoor air, the space temperature will
rise or fall depending on the outside air temperature. The
IAQ High Temperature Lockout Set Point is the maximum
outdoor air temperature reading at which a zone will allow
air to be brought into the zone to satisfy IAQ requirements.
The IAQ High Temperature Lockout Set Point option will
keep the IAQ mode from beginning unless the outdoor tem-
perature is below the set point. The option is configured in
category 14, option 7. The set point can be configured from
0 to 110 F. The default value is 80 F.
IAQ ALARM DELAY The IAQ Alarm Delay option con-
trols how long the monitor thermostat will wait before is-
suing an IAQ alarm. To configure the IAQ Alarm Delay op-
tion, set category 14, option 8. The number of minutes will
be shown. The range of acceptable values is 0 to
240 minutes in 1 minute increments. Use the left set point
buttons to set the time limit to the desired value. The default
value is 0 minutes.
NOTE: The alarm is issued only after the local IAQ alarm
is active for the entire alarm delay.
Fan/Filter Status Switch The fan/filter status switch
can be configured to signal when the system fan is operating
or to monitor the HVAC equipment filter and send a dirty
filter alarm.
NOTE: The humidity sensor and fan/filter status sensor can-
not be wired at the same time, only one sensor can be used.
To configure to monitor thermostat to use a fan/filter sta-
tus switch, set category 5, option 11. A value of 0 configures
the system for no sensor. A value of 1 configures the system
for an indoor humidity sensor. A value of 2 configures the
system for a fan/filter status switch. The default is 0.
Category 5, option 10 configures whether the fan status or
filter status capability of the sensor is used. Set the option to
ON for a fan status switch. Set the option to OFF for a filter
status switch. The default is OFF.
Refer to the fan/filter status installation instructions for
more information.
24