Specifications

Device Bus Number There can be many different
communication busses connected in a single system. There
is one primary bus and up to 239 secondary busses which
reside on the primary bus. The primary bus is always bus
number 0. The secondary bus address must be between
1 and 239. The monitor thermostat bus address must be en-
tered into the Device Bus Number configuration. The
default is 0. Acceptable values range from 0 to 239. The
Device Bus Number is set in category 8, option 3.
A maximum of 32 devices, with no more than 8 monitors
(scanners), are allowed on each communication bus. The maxi-
mum length of a communication bus is 4000 ft (four
1000 ft segments joined by 3 CCN repeaters). Secondary buses
can be established by using a bridge module and also have
the same 32 devices, with no more than 8 monitors (scan-
ners), capacity.
The primary number is always 0. Secondary network buses
can be added by using a network bridge module. This sec-
ondary bus has a bus number equal to the device address of
the bridge module. Any thermostats (monitor, zone control-
ler, bypass controller) on this secondary bus must have their
device bus number set equal to the device address of the bridge
module.
Device Access Security Level The device ac-
cess security level is used to limit access to the monitor ther-
mostat functions by unauthorized personnel. The security level
is configured in category 8, option 2. The factory setting
is 1. The range of acceptable security levels is 1 to 4.
The following details the amount of access limitation each
security level provides when programming locally at the moni-
tor thermostat (other network systems, such as Building Su-
pervisor, can still access and program the monitor thermo-
stat functions).Access security level 1 allows full programming
of the monitor thermostat. Access security level 2 allows pro-
gramming of occupied set points, occupancy schedules, and
holiday schedules. Access security level 3 allows program-
ming of occupied heating and cooling set points only. Ac-
cess security level 4 allows no programming.
Do not leave the access security level option at 1 after
configuration is complete. Untrained or unauthorized
users may change set points or other important
information.
If the access security level is changed from 1, the access
security level cannot be changed in the normal method be-
cause programming is locked out (for local programming only).
To reconfigure the access security level of the monitor ther-
mostat, activate the alternate information display by simul-
taneously pressing the upper and lower set point buttons. Once
the alternate information is activated the monitor thermostat
will begin to display a sequence of information in the order
described in the Alternate Information Display section on
page 15. When the display shows the access security level
number, press any button to freeze the display. Then press
both the heating and cooling buttons to enter the Program-
ming mode. Reconfigure category 8, option 2 to the desired
security level. Be sure to hit the enter button after the de-
sired security level has been made.
Monitor Type (Scanning Control) The Monitor
Thermostat can be configured to operate as 3 different system-
specific types of monitors:
as a VVTt Monitor Thermostat. The monitor is used in a
VVT system to control the heating/cooling equipment op-
eration based on its zone requirements and the require-
ments of the associated zone controllers.
as a VVT Monitor-Only Thermostat. The monitor thermo-
stat is used in a VVT system to control the heating/cooling
equipment operation based on the zone demand of the as-
sociated zone controllers.
as a VVT Construction thermostat (on a temporary basis).
The monitor thermostat is used in a construction site to
control the heating/cooling equipment operation based on
its own zone requirements. It is used to provide heating or
cooling to a site before all the remaining associated con-
trollers and system elements are installed.
The monitor thermostat is configured to operate as one of
the 3 system types by configuring the Scanning Control op-
tion. The Scanning Control option is configured in category
8, option 4. The settings are 1, 2, or 3. Setting 1 will cause
the thermostat to act as a VVT monitor thermostat. Setting
2 will cause the thermostat to act as a VVT monitor-only
thermostat. Setting 3 will cause the thermostat to act as a
VVT construction thermostat.
VVT MONITOR THERMOSTAT SYSTEM The moni-
tor thermostat, configured for VVT Monitor operation, in a
VVT system application will:
control the occupied and unoccupied mode conditions in
its zone by modulating a zone damper.
initiate communication with the associated zone control-
lers to distribute system information or instructions and
collect zone information.
determine the system requirements for heating and cool-
ing based on its own zone information and the informa-
tion gathered from the associated zone controllers. See
Fig. 17.
To configure the monitor thermostat for VVT Monitor op-
eration, configure the Scanning Control option (category 8,
option 4) to 1.
VVT MONITOR ONLY SYSTEM The monitor thermo-
stat, configured for VVT Monitor Only System operation, in
a VVT system application will:
initiate communication with the associated zone control-
lers to distribute system information or instructions and
collect zone information.
determine the system requirements for heating and cool-
ing based on the information gathered from the associated
zone controllers. See Fig. 18.
To configure the monitor thermostat for Monitor Only op-
eration, configure the Scanning Control option (category 8,
option 4) to 2.
VVT MONITOR CONSTRUCTION SYSTEM The moni-
tor thermostat, configured for VVT Monitor Construction Sys-
tem operation, in a VVT system application will:
determine the system requirements for heating and cool-
ing based on the information gathered from its own zone
sensors.
NOTE: In construction mode, the monitor thermostat does
not refer to programmed system lockout or trip limits.
NOTE: When a monitor thermostat is configured for con-
struction mode the supply air duct sensor will issue a HF-05
alarm (duct temperature sensor out of range) when a duct
sensor is not connected.
To configure the monitor thermostat for Monitor Con-
struction operation, configure the Scanning Control option
(category 8, option 4) to 3.
16