Specifications
Table 1 — VVTT Monitor Thermostat Categories and Options (cont)
OPTION DESCRIPTION DEFAULT MINIMUM MAXIMUM
CATEGORY 6.0 SUPPLEMENTAL HEAT
6.1 Supplemental Heat Lockout OFF OFF ON
6.2 Supplemental Heat Callers OFF OFF ON
CATEGORY 7.0 DIAGNOSTICS/METERING
7.1 Error Code Display OFF OFF ON
7.2 Communications Check OFF OFF ON
7.3 Alternate Information OFF OFF ON
7.4 Occupied Trend Demand (1/10°F) 0 0 25.5
7.5 Occupied Trend Time Limit (Minute) 2 2 255
7.6 HVAC Usage Meter OFF OFF ON
7.7 Override Usage Meter OFF OFF ON
7.8 HVAC Override Usage Meter OFF OFF ON
7.9 Heat Mode Error Set Point (F) 0 0 140
7.10 Cool Mode Error Set Point (F) 140 0 140
7.11 Unit Reset OFF OFF ON
CATEGORY 8.0 START-UP
8.1 Device Element Address 0 0 239
8.2
Access Security Level (1 — All Programming Allowed, 2 — Programming
of Occupancy Schedules and Set Points Only, 3 — Programming of Set
Points Only,4—NoProgramming Allowed)
11 4
8.3 Device Bus Number 0 0 239
8.4
Scanning Control (1 — Associated Zone,2—NoAssociated Zone,
3 — Construction Mode)
11 3
CATEGORY 9.0 BROADCAST / DAYLIGHT SAVINGS TIME
9.1 Broadcast Acknowledger OFF OFF ON
9.2 Global Schedule Broadcaster OFF OFF ON
9.3 Network Time Request OFF OFF ON
9.4 Receive Network Time ON OFF ON
9.5 Network Time Broadcast OFF OFF ON
9.6 Daylight Savings Time Start Month 4 1 12
9.7 Daylight Savings Time Start Week 1 1 5
9.8 Daylight Savings Time Start Day 7 1 7
9.9 Daylight Savings Time Minutes To Add 60 0 90
9.10 Daylight Savings Time Stop Month 10 1 12
9.11 Daylight Savings Time Stop Week 5 1 5
9.12 Daylight Savings Time Stop Day 7 1 7
9.13 Daylight Savings Time Minutes Subtracted 60 0 90
CATEGORY 10.0 HOLIDAY SCHEDULES
10.1-10.18
Holiday Schedule 1-18
Holiday Start Month
Start Day
Duration (Days)
0
0
0
0
0
0
12
31
99
CATEGORY 11.0 ALARM
11.1 Equipment Priority 7 0 7
11.2 Communication Failure Retry Time (Minutes) 10 1 240
11.3 Re-Alarm Time (Minutes) 30 1 255
CATEGORY 12.0 OPTIMAL START
12.1 Optimal Start Time Limit (Hrs) 4 0 4
CATEGORY 13.0 LOADSHED
13.1 Demand Limit Group Number 0 0 16
CATEGORY 14.0 INDOOR AIR QUALITY (IAQ)
14.1 System Indoor-Air Quality Participation ON OFF ON
14.2 System Indoor-Air Quality Sensor† OFF OFF ON
14.3 Indoor-Air Quality Economizer Delay (Minutes) 10 5 30
14.4 Indoor-Air Quality Maximum Space Temperature Reset (F) 2 0 10
14.5 Indoor-Air Quality Humidity Lockout Set Point 0 0 100
14.6 Indoor-Air Quality Low Temperature Lockout (OAT) (F) 45 0 110
14.7 Indoor-Air Quality High Temperature Lockout (OAT) (F) 80 0 110
14.8 Indoor-Air Quality Alarm Delay (Minutes) 0 0 240
*Schedule number 0 will cause the monitor thermostat to run as always occupied. Schedule numbers 1-64 will tell the monitor thermostat to use
local schedule number 1. Schedule numbers 65-99 will tell the monitor thermostat to use global schedules 65-99 respectively.
†Only for applications using a 33CSUCE-06 (TSR-01W) or TSR-01.