Operating instructions

PROCEDURE 3LIMIT CONTROLS ADJUSTMENT
Instructions for each control are included with controls.
Table 6 shows recommended boiler water temperatures. These settings can be changed after becoming familiar with system operation. For
example, if system is not giving quite enough heat in very cold weather, the limit setting can be raised to 220°F. Use boiler gage to check settings.
Make adjustments according to its readings.
Check thermostat operation. When set above temperature indicated on thermometer, boiler should ignite. Make certain thermostat turns boiler off
when room temperature reaches selected setting and starts boiler operating when room temperature falls a few degrees.
After setting limit control to limit setting, check to see if it shuts off gas supply to burners. Set thermostat to call for heat and let boiler run until
temperature of water reaches limit setting. Gas valve should shut off, and circulator should keep running until thermostat is satisfied or water cools
enough to restart burners through limit control.
Finally, set thermostat for desired temperature. Special conditions in home and location of thermostat govern this setting.
MAINTAINING BOILER
PROCEDURE 1BURNERS
A visual check of pilot and main burner flames should be made at least once each year, preferably at beginning of heating season. See Checking
and Adjusting section.
PROCEDURE 2RELIEF VALVE
This valve should open automatically when system pressure exceeds pressure rating (usually 30 psi) of relief valve. Should it ever fail to open under
this condition, shut down system. Drain system until pressure is reduced below relief valve pressure rating. If valve discharge occurs or if valve
fails to open as described above, contact an authorized contractor or qualified service technician to replace relief valve and inspect heating system
to determine the cause, as this may indicate an equipment malfunction.
This valve should be tested every month during periods of boiler operation, and at the beginning and end of any extended non-service period. Prior
to testing, make certain discharge pipe is properly connected to valve outlet and arranged so as to contain and safely dispose of boiler discharge.
Test at normal system operating pressure. Hold trip lever fully open for at least 5 sec in order to flush free any sediment that may lodge on valve
seat, then permit valve to snap shut.
PROCEDURE 3EXPANSION TANK
As previously noted, this tank may become waterlogged or may receive an excess of air. Frequent automatic opening of relief valve indicates
waterlogging. A high boiler temperature accompanied by unusually low radiation unit temperature (and "knocking") indicates excess air in tank.
To correct either condition, close valve between boiler and tank. Drain tank until it is empty. Check all tank plugs and fittings. Tighten as necessary.
Open valve between boiler and tank. Water will rise to normal height in tank if automatic fill valve is installed, otherwise, manually refill system.
PROCEDURE 4BOILER FLUE PASSAGES
Under normal operating conditions with burners properly adjusted, it should not be necessary to clean boiler flue gas passages. However, to assure
trouble-free operation, we recommend that flue passages, burner adjustment, and operation of controls be checked ONCE EACH YEAR by a
competent service technician.
BEFORE THE START OF EACH SEASON (or whenever system has been shut down for some time), recheck whole system for leaks and recheck
boiler and vent pipe for leaks. Replace or patch any boiler seals that are faulty.
PROCEDURE 5VENT PIPE
The venting of this unit is very important. Piping should be checked at least once a season. If vent piping shows any signs of leaking, replace it
immediately.
PROCEDURE 6WATER SYSTEM
If system is to remain out of service during freezing weather, always DRAIN IT completely. Water left in to freeze will crack pipes and/or boiler.
PROCEDURE 7CLEANING BOILER AND BURNERS
Flue passages between sections should be examined yearly and cleaned if necessary. To clean:
1. Remove burners, pilot, and vent pipe.
2. Remove top and front jacket panels.
Fig. 14Pilot Flame and Sensor
A95160
3
8 to
1
2
FLAME
ON SENSOR
Fig. 15Main Burner Flame
A99182
OUTER MANTEL
SHARP INNER CONES
Table 6Recommended Boiler Water Temperatures
TYPE OF HEATING UNIT LIMIT CONTROL SETTING
Standing Radiators 180°F
Baseboard and Convector Radiators 200°F
19