6. Turn gas control knob clockwise to OFF position. (See Fig. 11.)
7. Wait 5 minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow "B" in safety information
in "For Your Safety Read Before Operating" section.
8. Turn gas control knob counterclockwise to ON position. (See Fig. 11.)
9. Replace lower front panel.
10. Turn on all electrical power to appliance.
11. Set thermostat to desired setting.
12. If appliance will not operate, follow instructions "To Turn Off Gas To Appliance" and call your service technician or gas supplier.
B. To Turn Off Gas To Appliance
1. Set thermostat to lowest setting.
2. Turn off all electric power to appliance if service is to be performed.
3. Turn gas control knob clockwise to OFF position. (See Fig. 11.)
PROCEDURE 2CONTINUOUS PILOT BOILERVR8200A/VR8300A GAS VALVE
A. To Turn On Gas To Appliance
1. STOP! Read safety information in "For Your Safety Read Before Operating" section.
2. Set thermostat to lowest setting.
3. Turn off all electrical power to appliance.
4. Remove lower front panel.
5. Turn gas control knob clockwise to OFF position. (See Fig. 12.)
6. Wait 5 minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow "B" in safety information
in For Your Safety Read Before Operating section.
7. Find pilot. Follow metal tube from gas control. The pilot is between 2 burner tubes. (See Fig. 14.)
8. Turn knob on gas control counterclockwise to PILOT position. (See Fig. 12.)
9. Push down and hold red reset button while you light pilot burner with a match. (See Fig. 13.) After about 1 minute, release reset button.
Pilot should remain lit. If it goes out, turn gas control knob clockwise to OFF position. To relight, repeat items 5-9.
If button does not pop up when released, stop and immediately call your service technician or gas supplier.
If pilot will not stay lit after several tries, turn gas control knob to OFF position and call your service technician or gas supplier.
10. After pilot remains lit when red button is released, turn gas control knob counterclockwise to ON position. (See Fig. 12.)
11. Replace lower front panel.
12. Turn on all electrical power to appliance.
13. Set thermostat to desired setting.
B. To Turn Off Gas To Appliance
1. Set thermostat to lowest setting.
2. Turn off all electrical power to appliance if service is to be performed.
3. Turn gas control knob clockwise to OFF position. (See Fig. 12.)
Fig. 11VR8204A/VR8304M Intermittent Ignition Gas Valve
A95520
GAS CONTROL
KNOB SHOWN
IN "ON" POSITION
PILOT
ADJUSTMENT
(UNDER CAP
SCREW)
GAS
INLET
INLET
PRESSURE
TAP
WIRING
TERMINALS (3)
OUTLET
PRESSURE
TAP
GROUND
TERMINALS (2)
GAS
OUTLET
PILOT
OUTLET
OFF
ON
PRESSURE REGULATOR
ADJUSTMENT
(UNDER CAP SCREW)
17