Specifications

63
APPENDIX B — CCN TABLES (cont)
CCN MAINTENANCE TABLES (cont)
CCN CONFIGURATION TABLES
TABLE DISPLAY NAME RANGE UNITS POINT NAME
DUALCHIL
Dual Chiller Link Good? No/Yes DC_LINK
Master Chiller Role 12-char ASCII MC_ROLE
Slave Chiller Role 12-char ASCII SC_ROLE
Lead Chiller Ctrl Point NNN.n degF LEAD_CP
Lag Chiller Ctrl Point NNN.n degF LAG_CP
Control Point NNN.n degF CTRL_PNT
Cool EnteringFluid-Slave NNN.n degF COOLEWTS
Cool Leaving Fluid-Slave NNN.n degF COOLLWTS
Cooler Entering Fluid NNN.n degF COOL_EWT
Cooler Leaving Fluid NNN.n degF COOL_LWT
Lead/Lag Leaving Fluid NNN.n degF DUAL_LWT
Percent Avail.Capacity NNN % CAP_A
Percent Avail.Cap.Slave NNN % CAP_A_S
Lag Start Delay Time 5-char ASCII LAGDELAY
Load/Unload Factor NNN SMZ
Load/Unload Factor-Slave NNNN SMZSLAVE
Lead SMZ Clear Commanded No/Yes LEADSMZC
Lag SMZ Clear Commanded No/Yes LAG_SMZC
Lag Commanded Off? No/Yes LAG_OFF
Dual Chill Lead CapLimit NNN.n % DCLDCAPL
Dual Chill Lag CapLimit NNN.n % DCLGCAPL
TABLE DISPLAY NAME RANGE DEFAULT UNITS POINT NAME
UNIT UNIT CONFIGURATION
Unit Type N Unit Dependent UNIT_TYP
Unit Size NNN Unit Size tons SIZE
Compressor A1 Size NNN Unit Size Dependent tons SIZE_A1
Compressor A2 Size NNN Unit Size Dependent tons SIZE_A2
Compressor A3 Size NNN Unit Size Dependent tons SIZE_A3
Suction Superheat Setpt NN.n 9.0 deg F deltaF SH_SP
Compressor A1 Digital? No/Yes Unit Dependent CPA1TYPE
Maximum A1 Unload Time NN 10 - 015 to 030
7 - 035 to 045
secs MAXULTME
OPTIONS1 OPTIONS 1 CONFIGURATION
Cooler Fluid N 1=Water 1=Water
2=Medium Temperature
Brine
FLUIDTYP
Minimum Load Vlv Select No/Yes No MLV_FLG
Return Gas Sensor Enable Disable/Enable Disable RGT_ENA
Enable OAT Sensor Disable/Enable Disable OAT_ENA
CSB Boards Enable Disable/Enable Enable CSB_ENA
Reverse Rotation Enable Disable/Enable Enable REVR_ENA
Cooler Pump Control Off/On Off CPC
Cooler Pump Shutdown Dly NN 1 mins PUMP_DLY
EMM Module Installed No/Yes No EMM_BRD
Enable Condenser Pump N 0=No Conrol 0=No Control
1=On When Occupied
2=On with Compressors
CONDPMPE
Enable Cond Wtr Sensors Disable/Enable Disable CONDWTRS
Enable Cond Flow Switch Disable/Enable Disable CONDFLSW
OPTIONS2 OPTIONS 2 CONFIGURATION
Control Method N 0 CONTROL
Loading Sequence Select N 1 SEQ_TYPE
Lead/Lag Circuit Select N 1 LEAD_TYP
Cooling Setpoint Select N 0 CLSP_TYP
Ramp Load Select Disable/Enable Enable RAMP_EBL
High LCW Alert Limit NN.n 60.0 deltaF LCW_LMT
Minutes Off time NN 0 mins DELAY
Deadband Multiplier N.n 1.0 Z_GAIN
Ice Mode Enable Disable/Enable Disable ICE_CNFG
SCHEDOVR TIME OVERRIDE SETUP
Schedule Number NN 1 SCHEDNUM
Override Time Limit N 0 hours OTL
Timed Override Hours N 0 hours OVR_EXT
Timed Override No/Yes No TIMEOVER