Specifications

30
GREEN - YELLOW
GREEN - YELLOW
GREEN
TA N
TA N
TA N
WHITE
RED
BLACK
GRAY
GRAY
GRAY
BLACK
BLACK
BLACK
BLACK
EXH.
FAN #1
EXH.
FAN #2
GRD.
GRD.
BLUE
BLUE
BROWN
BROWN
RELAY
TO HVAC UNIT
CONTROL BOX
(SEE NOTE 4)
TO ECONOMISER2
ACTUATOR
(SEE NOTE 2)
24 VAC
HOT
24 VAC
COM
EXH FAN
+
3
1
2
3
AB
1
3
7
9
4
6
3
3
1
1
2
2
4
4
4
BLACK
RED
END
SWITCH
PLUG
ECONOMISER2
CONTROLLER
(SEE NOTE 2)
POWER LINE
PLUG
C1
C2
TRANSFORMER
NO. HT01AH859
1
2
4
(SEE
NOTE 3)
575V
TO 575V POWER
PRIMARY
SECONDARY
220V
BLACK
RED
1
2
4
3
OR
FIELD
SUPPLIED
FUSED
DISCONNECT
FIELD SUPPLIED
2 x 4 JUNCTION BOX
GROUND
FOR 575-V POWER SUPPLY
FOR 208/230-V SEPARATE
POWER SUPPLY
NOTES:
1. 575 V transformer No. HT01AH859 is ordered separately from power exhaust.
2. EconoMi$er2 actuator and controller are shipped with the EconoMi$er2 not with power exhaust.
3. Connections from End Switch plug to the EconoMi$er2 controller are made by installer.
4. If a single power source is to be used, size wire to include power exhaust MCA and MOCP.
Check MCA and MOCP when power exhaust is powered through the unit. Determine the new MCA including the power exhaust using the fol-
lowing formula:
MCA New = MCA unit only + MCA of Power Exhaust
For example, using a 48HJD006---5 unit with MCA = 28.9 and MOCP = 35, with CRPWREXH030A00 power exhaust.
MCA New = 28.9 amps + 1.6 amps = 30.5 amps
If the new MCA does not go over the MOCP published, then MOCP would not change. The MOCP in this example is 35 amps, the MCA New
is below 35, therefore the MOCP is OK. If MCA New is larger than the published MOCP, raise the MOCP to the next larger size. For separate
power, the MOCP for the power exhaust will be 15 amps per NEC.
Fig. 35 EconoMi$er2 Power Exhaust Wiring 208/230 V and 575 V Units