Product data

94
COOLING CAPACITIES
50HJQ004 (3 Tons)
Temp (F)
Outdoor
Entering Air
(Edb)
Indoor Entering Air — Cfm/Bf
900/0.13 1200/0.17 1500/0.19
Indoor Entering Air — Ewb (F)
72 67 62 72 67 62 72 67 62
75
TC 41.7 38.4 34.1 43.2 40.3 37.3 44.4 41.4 36.8
SHC 20.3 25.0 29.0 21.9 28.0 33.7 23.2 30.6 36.8
kW 2.22 2.17 2.13 2.23 2.20 2.17 2.25 2.21 2.18
85
TC 40.5 37.2 32.4 42.1 39.0 36.0 43.1 40.2 37.2
SHC 19.9 24.6 28.1 21.6 27.8 33.2 23.1 30.5 36.3
kW 2.49 2.45 2.40 2.51 2.48 2.44 2.53 2.49 2.45
95
TC 39.1 35.9 30.6 40.8
37.6 33.9 42.0 38.7 35.8
SHC 19.4 24.1 27.2 21.2
27.4 32.2 23.0 30.2 35.8
kW 2.80 2.75 2.69 2.82 2.78 2.74 2.85 2.80 2.76
105
TC 37.6 33.9 28.8 39.2 36.0 32.3 40.1 37.0 34.6
SHC 18.8 23.3 26.3 20.8 26.8 31.4 22.3 29.7 34.5
kW 3.13 3.08 3.01 3.16 3.11 3.06 3.18 3.13 3.09
115
TC 35.9 31.9 27.9 37.4 34.2 30.2 38.3 35.3 32.5
SHC 18.2 22.5 25.8 20.2 26.1 30.1 21.8 29.0 32.5
kW 3.49 3.43 3.36 3.52 3.47 3.40 3.54 3.50 3.45
125
TC 34.2 30.5 26.3 35.5 32.1 28.6 36.3 33.2 31.0
SHC 17.6 21.9 25.0 19.5 25.3 28.6 21.4 28.2 31.0
kW 3.88 3.81 3.74 3.91 3.85 3.79 3.92 3.88 3.84
50HJQ005 (4 Tons)
Temp (F)
Outdoor
Entering Air
(Edb)
Indoor Entering Air — Cfm/Bf
1200/0.13 1600/0.16 2000/0.19
Indoor Entering Air — Ewb (F)
72 67 62 72 67 62 72 67 62
75
TC 53.1 48.7 45.0 55.6 49.6 46.7 56.1 50.7 48.4
SHC 25.1 30.7 36.7 27.3 32.6 40.5 28.2 35.1 44.6
kW 2.92 2.86 2.82 2.96 2.87 2.84 2.96 2.88 2.87
85
TC 51.9 47.3 43.7 53.9 49.1 45.6 54.4 50.2 46.9
SHC 24.9 30.2 36.2 26.7 33.4 40.4 27.7 36.1 44.2
kW 3.29 3.22 3.19 3.32 3.25 3.21 3.32 3.27 3.23
95
TC 50.5 45.5 42.1 51.8
47.4 44.0 52.3 47.4 44.6
SHC 24.3 29.5 35.6 26.0 32.8 39.9 27.0 34.3 42.4
kW 3.70 3.62 3.58 3.71
3.65 3.61 3.72 3.64 3.61
105
TC 48.2 43.7 40.5 50.0 45.3 42.2 50.8 46.3 43.2
SHC 23.6 28.9 35.1 25.7 32.0 39.5 27.2 34.8 42.4
kW 4.14 4.06 4.04 4.16 4.08 4.05 4.18 4.10 4.06
115
TC 45.1 42.1 38.2 46.4 43.5 39.9 46.0 44.4 41.3
SHC 22.1 28.7 34.0 23.6 31.9 38.6 23.8 34.4 41.3
kW 4.57 4.55 4.50 4.59 4.56 4.52 4.58 4.57 4.54
125
TC 43.2 39.5 36.1 43.9 41.2 37.7 44.9 41.8 39.6
SHC 21.7 27.7 33.0 23.0 31.3 37.6 24.5 33.9 39.6
kW 5.10 5.05 5.02 5.11 5.08 5.05 5.13 5.09 5.08
50HJQ006 (5 Tons)
Temp (F)
Outdoor
Entering Air
(Edb)
Indoor Entering Air — Cfm/Bf
1500/0.03 2000/0.05 2500/0.07
Indoor Entering Air — Ewb (F)
72 67 62 72 67 62 72 67 62
75
TC 70.4 62.3 52.9 73.6 68.2 58.4 75.5 69.1 64.9
SHC 34.2 42.0 48.1 37.8 49.6 57.6 41.1 53.8 64.8
kW 3.75 3.73 3.58 3.80 3.80 3.69 3.83 3.74 3.75
85
TC 68.5 58.9 50.8 71.0 65.4 56.5 72.7 66.9 62.7
SHC 33.6 40.6 47.1 37.1 48.5 56.4 40.3 53.9 62.6
kW 4.20 4.16 4.03 4.24 4.23 4.12 4.27 4.20 4.17
95
TC 65.8 55.3 47.4 68.8
62.2 53.5 70.5 64.0 60.3
SHC 32.8 39.2 45.5 36.6
47.3 53.5 40.2 53.1 60.2
kW 4.69 4.63 4.49 4.75 4.70 4.60 4.78 4.68 4.67
105
TC 63.0 51.4 43.6 65.6 58.1 50.2 67.1 60.7 57.5
SHC 31.7 37.6 43.6 35.6 45.8 50.2 39.1 52.1 57.5
kW 5.22 5.13 5.00 5.27 5.21 5.12 5.30 5.22 5.20
115
TC 59.4 48.2 40.8 62.1 52.6 46.8 63.7 55.5 52.6
SHC 30.6 36.4 40.8 34.6 43.7 46.8 38.4 50.3 52.5
kW 5.83 5.70 5.59 5.87 5.77 5.70 5.89 5.81 5.77
125
TC 53.8 44.6 40.4 56.8 46.3 43.3 59.5 47.8 47.3
SHC 28.7 35.0 40.3 33.0 41.3 43.3 37.3 46.9 47.3
kW 6.44 6.30 6.21 6.50 6.36 6.32 6.54 6.40 6.39
Performance data
Standard Ratings
LEGEND
NOTES:
1. Direct interpolation is permissible. Do not
extrapolate.
2. The following formulas may be used:
Where: h
ewb
= Enthalpy of air entering evapo-
rator coil
3. The SHC is based on 80 F edb temperature of
air entering evaporator coil.
Below 80 F edb, subtract (corr factor x cfm)
from SHC.
Above 80 F edb, add (corr factor x cfm) to
SHC.
Correction Factor = 1.10 x (1 BF) x
(edb – 80).
Bf Bypass Factor
Edb Entering Dry-Bulb
Ewb Entering Wet-Bulb
kW Compressor Motor Power Input
SHC Sensible Heat Capacity (1000 Btuh) Gross
TC Total Capacity (1000 Btuh) Gross
t
ldb
=t
edb
sensible capacity
(Btuh)
1.10 x cfm
t
lwb
= Wet-bulb temperature
corresponding to enthalpy of air
leaving evaporator coil (h
lwb
)
h
lwb
=h
ewb
total capacity
(Btuh)
4.5 x cfm
50TFQ004-01250HJQ004-012