Product data

86
ARI* capacity ratings
50HJQ004-006
50HJQ007-012
LEGEND
*Air Conditioning and Refrigeration Institute.
†Applies only to units with capacity of 60,000 Btuh or less.
NOTE:
Rated in accordance with ARI Standard 210/240-95 and 270-95. Rat-
ings are net values, reflecting effects of circulating fan heat. Supple-
mentary electric heat is not included. Ratings based on:
Cooling Standard: 80 F db (dry bulb), 67 F wb (wet bulb) indoor
entering-air temperature and 95 F db outdoor entering-air temperature.
IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and
80 F db outdoor entering-air temperature.
High-Temp Heating Standard: 70 F db indoor entering-air temperature
and 47 F db, 43 F wb outdoor entering-air temperature.
Low-Temp Heating Standard: 70 F db indoor entering-air temperature
and 17 F db, 15 F wb outdoor entering-air temperature.
ALL the 50HJQ and 50TFQ004,005 and 006 units are in compliance
with ASHRAE 90.1 2001 Energy Standard for minimum SEER and EER
requirements. Refer to state and local codes or visit the following web-
site: http://solstice.crest.org/efficiency/bcap
to determine if compliance
with this standard pertains to a given geographical area of the United
States.
California, Maryland, Washington, Wyoming, Massachusetts and vari-
ous local and state building codes adopted the ASHRAE 90.1 efficiency
standard on October 29, 2001.
UNIT
50HJQ
NOMINAL
TONS
COOLING HEATING (High Temp)
SOUND
RATING
(Bels)
Cap.
(Btuh)
SEER†
Cap.
(Btuh)
HSPF†
004 3 36,000 12.0 34,000 7.6 7.6
005 4 46,000 12.0 46,000 7.6 7.6
006 5 60,000 11.9 60,000 7.6 8.0
UNIT
50HJQ
NOMINAL
TONS
COOLING
HEATING
(High)
HEATING
(Low)
SOUND
RATING
(Bels)
IPLV
Cap.
(Btuh)
EER
Cap.
(Btuh)
COP
Cap.
(Btuh)
COP
007 6 71,000 10.5 69,000 3.4 37,000 2.2 8.0
008 7
1
/
2
88,000 10.3 85,000 3.3 48,000 2.2 8.2
012 10 116,000 10.3 114,000 3.3 64,000 2.2 8.4 10.4
Bels Sound Levels (1 bel = 10 decibels)
Cap. Net Capacity (Btuh)
COP Coefficient of Performance
EER Energy Efficiency Ratio
HSPF Heating Seasonal Performance Factor
IPLV Integrated Part-Load Values
SEER Seasonal Energy Efficiency Ratio
Model number nomenclature
HJQ High Efficiency Heat Pump
50Electric Cooling
1 Revision Number
FIOP Code*
Nominal Capacity
004 3 Tons 007 6 Tons
005 4 Tons 008 7 1/2 Tons
006 5 Tons 012 10 Tons
V-Ph-Hz
3 208/230-1-50
5 208/230-3-60
6 460-3-60
50HJQ004Z--311AA
Packaging
1 Domestic Unit
3 Export
6 LTL
Controls and Sensors
None
G Hinged Access Panels
H Hinged Panels & PremierLink
K Novar ETM2024 Control
L Novar ETM2024 Control & Hinged Panels
N Novar ETM3051 Control
P PremierLink DDC Control
R Novar ETM3051 & Hinged Panels
Y Apollo Control & Hinged Panels
Z Apollo Control
Indoor Motor Options
Standard Motor and Drive
M High Static Motor
Coil Options
Aluminum Fin/Aluminum Fin
B Copper Tube/Copper Fin
(Both Outdoor and Indoor Coils)
C Copper Tube/Copper Fin (Outdoor Coil Only)
F E-Coat Aluminum Fin/Copper Tube
G E-Coat Copper Fin/Copper Tube (Outdoor Coil Only)
V Pre-coated Copper Tube/Aluminum Fin
(Outdoor Coil Only)
*Refer to 50HJQ Price Pages for FIOP (factory-installed option) code table.
Quality Assurance
®
I
S
O
9
0
0
1
:
2
0
0
0
#
A
2
3
2
5
50TFQ004-01250HJQ004-012