Product data
32
ARI* capacity ratings
50TFQ004-006
50TFQ007-012
LEGEND
*Air Conditioning and Refrigeration Institute.
†Applies only to units with capacity of 60,000 Btuh or less.
**The IPLV applies only to 2-stage heat pump units.
NOTES:
1. Rated in accordance with ARI Standards 210/240-95 and 270-95.
2. Ratings are net values, reflecting the effects of circulating fan heat.
3. ALL the 50HJQ and 50TFQ004,005 and 006 units are in compliance with ASHRAE 90.1
2001 Energy Standard for minimum SEER and EER requirements. Refer to state and local
codes or visit the following website: http://solstice.crest.org/efficiency/bcap to determine if
compliance with this standard pertains to a given geographical area of the United States.
California, Maryland, Washington, Wyoming, Massachusetts and various local and state
building codes adopted the ASHRAE 90.1 efficiency standard on October 29, 2001.
4. Ratings are based on:
Cooling Standard: 80 F db, 67 F wb indoor entering-air temperature and 95 F db air entering
outdoor unit.
IPLV Standard: 80 F db, 67 F wb indoor entering-air temperature and 80 F db outdoor enter-
ing-air temperature.
High-Temp Heating Standard: 70 F db indoor entering-air temperature and 47 F db, 43 F wb
outdoor entering-air temperature.
Low-Temp Heating Standard: 70 F db indoor entering-air temperature and 17 F db, 15 F wb
outdoor entering-air temperature.
UNIT
50TFQ
NOMINAL
TONS
COOLING
HEATING
(High Temp)
SOUND
RATING
(Bels)
Capacity
(Btuh)
SEER†
Capacity
(Btuh)
HSPF
Belt
Drive
Direct
Drive
004 3 35,600 10.20 10.00 34,400 6.7 8.4
005 4 46,500 10.00 9.70 46,500 7.0 8.0
006 5 57,000 10.00 9.90 57,000 7.5 8.2
UNIT
50TFQ
NOMINAL
TONS
COOLING
HEATING
(High)
HEATING
(Low)
IPLV**
SOUND
RATING
(Bels)
Capacity
(Btuh)
EER
Capacity
(Btuh)
COP
Capacity
(Btuh)
COP
007 6 70,000 9.05 72,400 3.20 42,000 2.14 — 8.2
008 7
1
/
2
86,000 9.00 78,000 3.00 39,000 1.80 9.3 8.6
009 8
1
/
2
96,000 8.90 96,000 3.00 55,000 2.00 8.85 8.6
012 10 112,000 9.00 105,000 3.10 59,000 2.00 9.0 8.4
Bels — Sound Levels (1 bel = 10 decibels)
COP — Coefficient of Performance
db — dry bulb
EER — Energy Efficiency Ratio
HSPF — Heating Seasonal Performance Factor
IPLV — Integrated Part-Load Values
SEER — Seasonal Energy Efficiency Ratio
wb — wet bulb
Model number nomenclature — 50TFQ units
50TFQ004Z- -501AA
TFQ – Standard Efficiency Heat Pump
50 – Electric Cooling
Design Series
0 – Original
Factory Installed Option Code*
Nominal Capacity
004 – 3 Tons 008 – 7 1/2 Tons
005 – 4 Tons 009 – 8 1/2 Tons
006 – 5 Tons 012 – 10 Tons
007 – 6 Tons
Factory-Installed Communicating Control
- – Standard
K – Novar ETM2024 Control
N – Novar ETM3051 Control
P – Carrier PremierLink™ Rooftop Controller
Z – Apollo Control
For more information about Novar Control option, check
with your sales representative.
V-Ph-Hz
1 – 575-3-60
3 – 208/230-1-50†
5 – 208/230-3-60
6 – 460-3-60
Coil Fin Options
- – Copper Tube/Aluminum Fin (Both Outdoor and Indoor Coils)
B – Copper Tube/Copper Fin (Both Outdoor and Indoor Coils)
C – Copper Tube/Copper Fin (Outdoor Coil Only)
F – E-Coat Copper Tube/Copper Fin (Both Outdoor and
Indoor Coils)
G – E-Coat Copper Tube/Copper Fin (Outdoor Coil Only)
V – Pre-coated Copper Tube/Aluminum Fin (Outdoor Coil Only)
Packaging
1 – Domestic
3 – Export
6 –LTL
Indoor Fan Motor
- – Standard Fan Motor
A – Alternate Fan Motor/Drive
M – High Static Fan Motor
®
I
S
O
9
0
0
1
:
2
0
0
0
#
A
2
3
2
5
LEGEND
*Refer to 50TFQ Price Pages or contact your local Carrier representative for
50TFQ code table.
†Single phase is only available on 5-ton and smaller units.
Al — Aluminum
Cu — Copper
FIOP — Factory-Installed Option
Quality Assurance
50TFQ004-01250TFQ004-012