Product data

134
ACCESSORY/FIOP STATIC PRESSURE* (in. wg) — 50HJQ014,016
LEGEND
*Units with electric heat are not designed to operate at these ranges.
NOTES:
1. Heaters are rated at 208/240 v, 480 v, and 600 v.
2. The static pressure must be added to external static pressure. The
sum and the indoor-air section entering-air cfm should then be
used in conjunction with the Fan Performance table to determine
blower rpm, bhp, and watts.
FAN RPM AT MOTOR PULLEY SETTINGS* — 50HJQ014,016
*Approximate fan rpm shown.
†Standard motor with standard drive.
**Standard motor with alternate drive.
ACCESSORY/FIOP UNIT SIZE UNIT VOLTAGE kW
CFM
3750 4500 5000 5600 6000 6250 7200 7500
Electric Heaters
014
208/230-3-60
14-34 0.05 0.05 0.07 0.08 0.09 0.09 0.11 0.12
42,56 0.06 0.06 0.08 0.10 0.12 0.13 0.16 0.17
460-3-60
15,32 0.05 0.05 0.07 0.08 0.09 0.09 0.11 0.12
55 0.06 0.06 0.08 0.10 0.12 0.13 0.15 0.15
575-3-60 37 0.06 0.06 0.08 0.10 0.12 0.13 0.15 0.17
016
208/230-3-60
26,34
***
0.08 0.09 0.09 0.11 0.12
42,59 0.10 0.12 0.13 0.16 0.17
460-3-60 32,55 * * *
0.08 0.09 0.09 0.11 0.12
0.10 0.12 0.13 0.15 0.17
575-3-60 50 * * * 0.13 0.15 0.16 0.20 0.21
Economizer All All 0.03 0.03 0.05 0.06 0.07 0.07 0.09 0.10
Glycol Coil All All 0.16 0.18 0.25 0.31 0.35 0.37 0.44 0.46
FIOP Factory-Installed Option
UNIT
50HJQ
MOTOR PULLEY TURNS OPEN
0
1
/
2
11
1
/
2
22
1
/
2
33
1
/
2
44
1
/
2
55
1
/
2
6
014 (208/230Vand460V) 1179 1150 1121 1093 1064 1035 1006 978 949 920 891
014 (208/230 V and 460 V)** 1559 1522 1488 1455 1422 1389 1356 1323 1289 1256 1227
014 (575 V)† 1429 1403 1376 1349 1323 1296 1269 1242 1215 1188 1159
016† 1038 1023 1001 979 956 934 912 890 868 846 817
016** 1303 1288 1266 1244 1222 1199 1177 1155 1133 1111 1082
Performance data (cont)
FAN PERFORMANCE USING ACCESSORY POWER EXHAUST
50TFQ004-01250HJQ014,016