Product data

125
Base unit dimensions — 50HJQ014,016
*Units with aluminum indoor and outdoor coil fins.
UNIT
50HJQ
MAXIMUM SHIPPING WEIGHT*
Lb Kg
014 1895 860
016 2205 1000
LEGEND
UNIT
50HJQ
DIMENSIONS
X Y
Ft-in. mm Ft-in. mm
014 3-1 947 3-2 965
016 3-6 1059 3-8 1105
KO—Knockout
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Center of gravity.
3. Direction of airflow.
4. Ductwork to be attached to accessory roof curb only.
5. Minimum clearance:
a. Rear: 7-0 (2134) for coil removal. This dimension can be
reduced to 4-0 (1219) if conditions permit coil removal
from the top.
b. Left side: 4-0 (1219) for proper outdoor coil airflow.
c. Front: 4-0 (1219) for control box access.
d. Right side: 4-0 (1219) for proper operation of damper
and power exhaust (if so equipped).
e. Top: 6-0 (1829) to assure proper outdoor fan operation.
f. Local codes or jurisdiction may prevail.
6. With the exception of clearance for the outdoor coil and the
damper and power exhaust as stated in note no. 5, a remov-
able fence or barricade requires no clearance.
7. Dimensions are from outside of corner post. Allow 0-
5
/
16
(8)
on each side for top cover drip edge.
*Weights are for unit only and do not include options or crating.
UNIT
50HJQ
WEIGHT OF CORNER*
ABCD
Lb KgLbKgLbKgLbKg
014 366 166 356 161 360 163 534 242
016 464 211 496 225 477 217 487 221
50TFQ004-01250HJQ014,016