Product data
114
UNITS WITH ELECTRICAL CONVENIENCE OUTLET (cont)
LEGEND AND NOTES FOR ELECTRICAL DATA TABLES
LEGEND
*Used to determine minimum disconnect per NEC.
†Heater capacity (kW) is based on heater voltage of 208 v, and 480 v.
If power istribution voltage to unit varies from rated heater voltage,
heater kw will vary accordingly.
**Fuse or HACR circuit breaker.
††Optional disconnect switch cannot be used.
***Units have 2 outdoor fan motors.
NOTES:
1. In compliance with NEC requirements for multimotor and combina-
tion load and equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%.
Use the following formula to determine the percent
of voltage imbalance.
% Voltage Imbalance
Example: Supply voltage is 460-3-60.
AB = 452 v
BC = 464 v
AC = 455 v
= 457
Determine maximum deviation from average voltage.
(AB) 457 – 452 = 5 v
(BC) 464 – 457 = 7 v
(AC) 457 – 455 = 2 v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
= 1.53%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
UNIT
NOMINAL
VOLTAGE
(V-Ph-Hz)
VOLTAG
E
RANGE
COMPRESSOR OFM IFM
ELECTRIC
HEAT*
POWER
SUPPLY
MINIMUM UNIT
DISCONNECT
SIZE
Min Max RLA LRA FLA FLA kW† FLA MCA MOCP FLA LRA
50HJQ008***
(7
1/
2
Tons)
208/230-3-60 187 254 12.4 88.0 1.4 7.5
—
/— —/— 43.0/ 43.0 45/ 45** 46/ 46 247/247
7.8/10.4 21.7/ 25.0 70.1/ 74.3 80/ 80 71/ 75 269/272
12.0/16.0 33.3/ 38.5 84.6/ 91.1 90/100 84/ 90 280/285††
18.6/24.8 51.6/ 59.7 107.5/117.6 110/125 105/115 298/307††
24.0/32.0 66.6/ 77.0 126.3/139.3 150/150 122/134 313/324††
31.8/42.4 88.3/102.0 153.4/170.5 175/175 147/163 335/349††
460-3-60 414 508 6.4 44.0 0.7 3.4
— — 21.4 25** 23 123
13.9 16.7 42.3 45** 42 140
16.5 19.8 46.1 50** 46 143
27.8 33.4 63.1 70 61 157
33.0 39.7 71.0 80 68 163
41.7 50.2 84.1 90 80 174††
50HJQ012***
(10 Tons)
208/230-3-60 187 254 19.3 123.0 1.4 10.6
—
/— —/— 61.6/ 61.6 70/ 70 65/ 65 341/341
7.8/10.4 21.7/ 25.0 88.8/ 92.9 90/100 90/ 94 363/366††
12.0/16.0 33.3/ 38.5 103.3/109.6 110/110 104/110 375/380††
24.0/32.0 66.6/ 77.0 144.9/157.9 150/175 142/154 408/418††
31.8/42.4 88.3/102.0 172.0/189.1 175/200 167/183 430/443††
37.6/50.0 104.4/120.3 192.1/181.9 200/200 185/204 446/462††
460-3-60 414 508 10.0 62.0 0.7 4.8
— — 30.9 35** 33 172
16.5 19.8 55.6 60** 55 191
27.8 33.4 72.6 80 71 205
33.0 39.7 80.5 90 78 211
41.7 50.2 93.6 100 90 222††
50.0 60.1 91.0 100 102 232††
FLA — Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM — Indoor Fan Motor
LRA — Locked Rotor Amps
MCA — Minimum Circuit Amps
MOCP— Maximum Overcurrent Protection
NEC — National Electrical Code
OFM — Outdoor Fan Motor
RLA — Rated Load Amps
= 100 x
max voltage deviation from average voltage
average voltage
Average Voltage =
452 + 464 + 455
3
=
1371
3
IMPORTANT: If the supply voltage phase imbalance is more than 2%,
contact your local electric utility company immediately.
7
457
Electrical data (cont)
50TFQ004-01250HJQ004-012